4 PROFIBUS-DP Option Components

16

YASKAWA ELECTRIC TOBP C730600 23C 1000-Series Option SI-P3/V, SI-P3/T Installation Manual

{: On / †: Flashing /

×: Off

Setting Node Address

Set drive parameter F6-30 to a unique node address (Range 0 to 125) on the network.

{

×

×

×

• Checking

connection with
the drive

• Waiting for data

from the master

• PROFIBUS-DP Option

is reading the node
address or parameter
configuration

• Waiting for initial input

data from master device

×

{

×

×

PROFIBUS-DP
Option Self-
diagnostics error

The PROFIBUS-DP
Option is damaged

Cycle power to the drive. If the LED
status does not change, replace the
PROFIBUS-DP Option

×

†

×

×

Problem connecting
to the drive

• Problem initializing the

drive and PROFIBUS-
DP Option

• Incorrect node address

• Cycle power to the drive. If the LED

status does not change, replace the
PROFIBUS-DP Option

• Check the node address setting in the

drive (parameter F6-10)

{

×

×

{

Waiting for data
from the master
device

Waiting for data from the
master device
(Set_Parm_Message or
Chk_Cfg_Message)

• Check the network settings in the

master

• Make sure the master device is

operating normally

• Check the terminal resistance settings

on the data line

• Look for any problems with the data

line, or if the connector

• Check that the data lines are properly

connected to the drive

{

×

×

†

Data is incorrect or
PROFIBUS-DP
Option timed out
waiting for data

The communication
procedure in the master is
set incorrectly

• Check the communication procedure

settings in the master

{

×

{

×

Sending or receiving
data

LED

Communication

Status

Possible Cause

Solution

RUN ERR COMM BF