5 Installation Procedure

24

YASKAWA ELECTRIC TOBP C730600 23C 1000-Series Option SI-P3/V, SI-P3/T Installation Manual

7.

Attach the PROFIBUS-DP Option cover to the front of the PROFIBUS-DP Option.

Figure 14

Figure 14 Attach Cover

Note: When using the drive in an area that may require displaying warning information in Japanese or

Chinese, a label is provided with the Profibus-DP Option. This label can be placed over the

English and French warnings on the front of the Profibus-DP Option.

Communication Cable Specifications

To ensure proper performance, Yaskawa recommends using PROFIBUS-DP-dedicated

cables that fulfill the specifications in

Table 6

. For more information on cables, refer to the

PROFIBUS-DP website at http://www.profibus.com.

Cable Requirements

Table 6 Communication Cable Requirements

Condition

Specifications

Impedance

135 to 165

Ω at a frequency of (3 to 20 MHz)

Capacity

30 pF/m maximum

Loop Resistance

110

Ω/km maximum

Core Cross-Section

0.34 mm

2

minimum

Core Diameter

0.64 mm minimum

Tabs should line up