8 Troubleshooting

8

Troubleshooting

Drive-Side Error Codes

Drive-side error codes appear on the drive LED operator. Causes of the errors and corrective

actions are listed in

Table 12

. For additional error codes that may appear on the LED

operator screen, refer to the technical manual for the drive.

Faults

bUS (PROFIBUS-DP Option Communication Error) and EF0 (External Fault Input from the

PROFIBUS-DP Option) may appear as an alarm or a fault. When a fault occurs, the digital

operator LEDs remain lit. When an alarm occurs, the digital operator LEDs flash and the

“ALM” light illuminates
If communication stops while the drive is running, check the following items to resolve the

fault:

• Is the PROFIBUS-DP Option properly installed?

• Is the communication line properly connected to the PROFIBUS-DP Option? Is it loose?

• Is the controller program working? Has the controller CPU stopped?

• Did a momentary power loss interrupt communications?

Table 12 Fault Display and Possible Solutions

LED Operator Display

Fault Name

bUS

PROFIBUS-DP Option Communication Error

• After establishing initial communication, the connection was lost
• Only detected when the run command or frequency reference is assigned

to the option (b1-03 = 3 or b1-02 = 3)

Cause

Possible Solution

Master controller (PLC) has stopped
communicating.

Check for faulty wiring.
Correct any wiring problems

Communication cable is not connected
properly

A data error occurred due to noise

Check the various options available to minimize the effects of noise.

• Take steps to counteract noise in the control circuit wiring, main circuit

lines, and ground wiring.

• If a magnetic contactor is identified as a source of noise, install a surge

absorber to the contactor coil

Use cables recommended by Yaskawa, or another type of shielded line.
Ground the shield on the controller side and on the PROFIBUS-DP Option
side

PROFIBUS-DP Option is damaged.

If there are no problems with the wiring and the error continues to occur,
replace the PROFIBUS-DP Option