5 Installation Procedure

22

YASKAWA ELECTRIC TOBP C730600 23C 1000-Series Option SI-P3/V, SI-P3/T Installation Manual

3.

Remove the bottom cover and connect the PROFIBUS-DP Option ground cable to
the ground terminal.

Figure 9

Figure 9 Connect Ground Cable

Note: The four different ground cables packaged with the PROFIBUS-DP Option connect to different

models. Select the proper ground cable from the PROFIBUS-DP Option kit depending on drive

size.

Figure 10

Figure 10 Ground Cable

Note: Cover removal for certain larger models with a Terminal Cover:

-Single-Phase 200 V Class: CIMR-V…BA0006 to BA0018, CIMR-T…BV0006 to BV0018

-Three-Phase 200 V Class: CIMR-V…2A0008 to 2A0069, CIMR-T…2V0008 to 2V0069

-Three-Phase 400 V Class: All models

Remove the terminal cover before removing the bottom cover to install the PROFIBUS-DP

Option. Replace the terminal cover after wiring the PROFIBUS-DP Option.

Figure 11

Figure 11 Models with Terminal Cover

A – Option unit connection: screw size = M3
B – Drive-side connection: screw size = M3.5 to M6

Ground terminal

Ground cable

Bottom cover

A

B