6 PROFIBUS-DP Option Drive Parameters

YASKAWA ELECTRIC TOBP C730600 23C 1000-Series Option SI-P3/V, SI-P3/T Installation Manual

27

F6-30

<4> <5>

Node Address

Select the node address of a PROFIBUS-DP Option.

Default: 0
Min: 0
Max: 125

F6-31

Clear Mode Selection

Selects the action to take when a "Clear Mode"
command is received
0: Resets back to 0
1: Maintains the previous value

Default: 0
Range: 0, 1

F6-32

<5>

PROFIBUS Map Selection

0: PPO Type
1: Conventional

Default: 0
Range: 0, 1

<1> To start and stop the drive through the PROFIBUS-DP network, set b1-02 to “3”. To control the frequency

reference of the drive via the PROFIBUS-DP network, set b1-01 to “3”.

<2> If F6-03 is set to 3, then the drive will continue to operate when an EF0 fault is detected. Take proper safety

measures, such as installing an emergency stop switch.

<3> Software versions 1012 and later have F6-07 and F6-08 both set to 1.

<4> All node addresses must be unique. Node addresses 0, 1, and 2 are typically reserved for control, maintenance, and

diagnostic equipment. The ERR light will illuminate when 0 or greater than 125 is entered.

<5> Power must be cycled in order for any setting changes to take affect.

<6> The V1000 and T1000V drives localized for Europe do not have the terminal S7 (Multi-function digital input

command 7).