5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 23C 1000-Series Option SI-P3/V, SI-P3/T Installation Manual

21

Prior to Installing the Option Unit

Prior to installing the PROFIBUS-DP Option, wire the drive and make necessary

connections to the drive terminals. Refer to the Yaskawa drive manual for information on

wiring and connecting the drive. Verify that the drive operates normally without the option

installed.

Installing the Option Unit

Remove the front cover of the drive before installing the PROFIBUS-DP Option. Follow the

directions below for proper installation.

1.

Switch off the power supply to the drive.

DANGER! Electrical Shock Hazard - Do not connect or disconnect wiring while the power is on. Failure to

comply will result in death or serious injury. Before installing the PROFIBUS-DP Option, disconnect all

power to the drive. The internal capacitor remains charged even after the power supply is turned off. The

charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock,

wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe

level.

2.

Remove the front cover. The original drive front cover may be discarded because it
will be replaced by the PROFIBUS-DP Option cover in step 7.

Figure 8

Figure 8 Remove Front Cover