LED Operator Display

Fault Name

EF0

External Fault Input from PROFIBUS-DP Option
The alarm function for an external device has been triggered

Cause

Possible Solution

An external fault is being sent from
the upper controller (PLC).

Remove the cause of the external fault

• Reset the external fault input from the upper controller (PLC) device

Problem with the upper controller
(PLC) program.

Check the program used by the upper controller (PLC) and make the
appropriate corrections

LED Operator Display

Fault Name

oFA00

PROFIBUS-DP Option Fault (Port A)
PROFIBUS-DP Option is not properly connected

Cause

Possible Solution

Non-compatible option connected to
the drive.

Connect an option that is compatible with the drive

LED Operator Display

Fault Name

oFA01

PROFIBUS-DP Option Fault (Port A)
PROFIBUS-DP Option is not properly connected

Cause

Possible Solution

Problem with the connectors between
the drive and PROFIBUS-DP Option.

Turn the power off and check the connectors between the drive and
PROFIBUS-DP Option.

LED Operator Display

Fault Name

oFA03

PROFIBUS-DP Option Fault (Port A)
PROFIBUS-DP Option self-diagnostics error

Cause

Possible Solution

PROFIBUS-DP Option hardware
fault.

Replace the PROFIBUS-DP Option. Contact Yaskawa for assistance

LED Operator Display

Fault Name

oFA04

PROFIBUS-DP Option Fault (Port A)
PROFIBUS-DP Option Flash write mode

Cause

Possible Solution

PROFIBUS-DP Option hardware
fault.

Replace the PROFIBUS-DP Option. Contact Yaskawa for assistance