3.0 Installation

2

1

3

4

3

1

2

1

3

4

5

2

B

ATTERY

N

EGATIVE

C

ONNECTION

TO

S

HUNT

B

USBAR

(B

OTTOM

)

3.7.3

DC Hardware Connections

Do not put anything between the DC cable lug and the DC terminals (i.e., on the Inverter DC
Disconnect, DC shunt busbars, batteries, or inverter terminals). Ensure the hardware used to hold
these connections is stacked correctly. Incorrectly installed hardware causes a high resistance
connection which could lead to poor inverter performance, and may melt the cable and terminal
connections. Follow Figure 3-20 to connect the DC cables and stack the hardware correctly.

Info:

After making the battery connections

and ensuring they are properly torqued,

cover the outside of the connection with petroleum jelly or an

antioxidant grease/spray.

Do not put jelly/anti-corrosion grease between the terminal and the battery cable.

Figure 3-20, DC Hardware Connections

I

NVERTER

DC N

EGATIVE

AND

P

OSITIVE

C

ONNECTIONS

B

ATTERY

P

OSITIVE

C

ONNECTION

TO

DC B

REAKER

(B

OTTOM

)

Bottom of Shunt Busbar

Hardware Stack-up:

1 DC Shunt Busbar

2 Hex Bolt (3/8-16)

3 Negative (-) Battery Cable Lug

4 Split-lock washer

5 5/16-18 Nut

DO NOT place anything between

the DC Shunt busbar and the

negative battery cable lug.

Inverter Hardware Stack-up:

1 Inverter DC Terminals

2

Inverter Cable Lugs

[(-) to Shunt Busbar,

(+) to Inverter DC Breaker]

3 5/16-18 Nut (Flange or Kep)

DO NOT Place anything between

the inverter DC terminals and the

inverter cable lugs.

Bottom of Inverter DC Breaker

Hardware Stack-up:

1 DC Breaker Terminal

2 Positive (+) Battery Cable Lug

3 Split-lock washer

4 Hex Bolt (3/8-16)

DO NOT place anything between

the DC breaker terminal and the

positive battery cable lug.