0 wiring diagrams, Left side view of inverter mounted on mp enclosure – Magnum Energy Magnum Panel (MP Series) User Manual

Page 76

Advertising
background image

© 2011 Magnum Energy, Inc.

Page 69

4.0 Wiring Diagrams

Figure 4-1, Inverter AC Input and Output Wiring Diagram - MS4024

MS4024 Series Inverter –

showing AC wires from the

internal AC wiring terminal

3

0

Left side view of

inverter mounted

on MP Enclosure

Inverter AC

Input Wires

(Leg 1 Only)

Inverter AC

Output Wires

(Leg 1 Only)

AC

GROUND

AC HOT 2 OUT

AC NEUT IN

AC NEUT OUT

AC HOT 1 OUT

AC HOT 1 IN

AC HOT 2 IN

.

B

L

AC

K

.

W
HIT

E

.

B

L

AC

K w

/S
T

RIP

E

.

W
HIT

E

w
/S
T

RIP

E

.

G

R

E

E

N

Info: When wiring the MS4024 (or any other MS Series inverter), both the inverter input
and output neutral wires must be connected to a AC NEUTRAL busbar inside the MP
enclosure. This is because — depending on the inverter’s operating mode — the inverter’s
input and output neutral terminals may not be connected together (i.e., inverter’s
neutrals are not connected when “inverting”, and are combined when “charging”).

Note: Because a neutral to ground connection is also made in the MP enclosure, the neutral to
ground connection inside the MS4024 must be disconnected. Refer to the MS4024 owner’s manual
for information on how this is done.