CI-ControlWave XFC

Basic CPU components and features are summarized as follows:

• LH7A400 System-on-Chip 32-bit ARM9TDMI RISC Core microprocessor
• 512KB FLASH Boot/Downloader, 29LV040B, 90 nS, 8-bit access
• 2MB SRAM, 3.3V, 1024K x 16, 17nsec., with Battery Back-up
• 8MB simultaneous read/write FLASH, TSOP site
• 3 serial Comm. ports
• SPI I/O Bus Interface, three separate chip selects
• Spread Spectrum clock for lower EMI
• Serial Real Time Clock with battery backup
• 10-Position general-purpose switch bank
• Coin cell socket accepts a 3.0V, 300mA-hr lithium battery
• Display

Module


1.3.3.1 CPU Board Connector P2


CPU Board connector P2 provides the interface to connector J7 on the XFC I/O Board (see
Table 1-1).

Table 1-1 - CPU Board Connector P2 - I/O Intf Signals (Pins 24 & 25 are not used)

I/O

# Pins

Signal Name

Description

I/O 1 GND

Power

Ground

O

2

VCC1.8

1.8 Volt Power

I

3

VCC3

3.3 Volt Power

O 4

IORSTB#.

I/O

Reset

I 5

POWERGOOD

Power

Good

I 6

PFDLYCLK#

PFDLYCLK#

I 7

PWRFAIL#

PWRFAIL#I

I 8

VIN100M

VIN100M

O 9

SPI_CK

SPI

Clock

I

10

SPI_MISO

SPI Master In / Slave Out

O

11

SPI_MISI

SPI Master Out / Slave In

O

12

SPI_IO_CS#

SPI Chip Enable for I/O Board

O 13

232

TXD2

COM1

I 14

232

RXD2

COM1

I 15

232

DCD3

COM2

I 16

232

RXD3

COM2

O 17

232

RTS3

COM2

O 18

232

TXD3

COM2

I 19

232

CTS3

COM2

O 20

232

DTR3

COM2

I/O 21 TR+

485

COM3

I/O 22 TR-

485

COM3

O

23

IO_CS#

Spare Chip Select

I/O 26 GND

Power

Ground


CPU Board Serial Comm. Port Connectors
(see Section 1.5.5)
The CPU Module supports up to three serial communication ports (COM1, COM2 &
COM3). COM1 provides a 3-wire half duplex RS-232 interface and is referenced on the
Terminal Plate as the Local Port. COM1 operates by sencing RS-232 levels on the TX or RX
terminals. COM2 provides a 7-wire RS-232 interface and supports half/full duplex
operation. When the ControlWave XFC has been configured for Auto DTR Mode, the DCD
signal must be high before COM2 becomes operational. COM3 supports RS-485