2-22 / Installation & Operation

CI-ControlWave XFC

ControlWave XFC’s utilize the common three-wire con-figuration. In this configuration,
the Return lead connects to RTD- and the two junction leads (Sense and Excitation),
connect to RTD+ and RTD EXC. Connection between the RTD and System Controller
Module is wired as follows:

Table 2-4- RTD Connections to Terminal Plate Connector J3

J3 Pin #

Signal

Function

Wire Color

3 RTD

EXC

Excitation

Red

2 RTD+ Sense Red
1 RTD- Return White

Never ground the RTD Cable Shield at both ends or allow it to come in contact with metal-
lic/conductive conduit as multiple ground paths could cause RTD input errors.

2.3.4.1 Bendable RTD Installation


WARNING: ONLY use a bendable RTD (supplied with a plastic bushing) for
Division 2 installations, as this will render the Housing Non-Explosion Proof. Use
an RTD Connection Head and Conduit for Division 1 installations.


To install the RTD Probe, screw the Fitting Body into the thermowell with a 7/8”open-end
wrench. While applying pressure against the sheath to force the Tip of the RTD Probe into
the bottom of the thermowell (so that the Probe Tip is in contact with the thermowell),
tighten the Nut (9/16” open-end wrench) against the 7/8” Fitting Body (see Figure 2-12).

Figure 2-11 - 3-Wire RTD Temperature Input Wiring


Figure 2-12 - RTD Probe Installation/Removal Diagram