3-4 / Service

CI-ControlWave XFC

3.3 TROUBLESHOOTING TIPS

3.3.1 Power Checks


One bulk power source can be connected to the Terminal Plate. Connector J6 provides 2 in-
put terminal connections for bulk power (see Figure 3-2):

J6-1 =

(+VIN) (+6Vdc to +30Vdc)

J6-2 = Chassis Ground – CHASSIS

Bulk supply voltages can be checked at J6 using a voltmeter or multimeter. The maximum
and minimum input power switch-points can be tested with the use of a Variable dc Power
Supply connected between J6-1 (+) and J6-2 (-). By increasing the input voltage (starting at
less than +5.4Vdc), you can determine the point at which the unit will turn on, i.e., the
point at which the LCD Display comes ON (Vt+). By decreasing the input voltage (starting
at +16Vdc), you can determine the point at which the unit turns off, i.e., the point at which
the LCD Display goes OFF (Vt-). If the value of the bulk power supply’s output approaches
the value of Vt+ or Vt- it should be replaced by a battery/power supply with the correct out-
put.

3.3.2 LCD Display System Status Codes


ControlWave XFCs contain an LCD Display that is utilized to display system status codes
and application data once the unit is running its application load. System status codes are
provided in Table 3-1.

Table 3-1 - LCD Display - System Status Codes

LCD

Display

Indication

Definition

Blank or Menu, etc.

Application Running

DIAG

Unit in Diagnostic Mode

R DIAG

Unit Running Diagnostics

FWXSUM

Flash XSUM Error

DEVERR

Error Initializing Application Device

FLASH

Flash Programming Error

FACT

Using Factory Defaults *

BATT

Battery Failure Detected *

STRTUP

Currently Loading Boot Project

INIT

System Initialization in Progress

RECOV

Waiting in Recovery Mode

RAMERR

Error Testing SRAM

STOP Application

Loaded

HALT

Stopped at a Break Point

NO APP

No Application Loaded

BREAKP

Running with Break Points

POWERD

Waiting for Power-down (after NMI)

UPDUMP

Waiting for Updump to be Performed

NOTRUN

Unit Crashed (Watchdog Disabled)

* = Flashed at startup

3.3.3 LED Checks


ControlWave XFCs contain two red LEDs that provide operational and diagnostic func-
tions as follows: