CI-ControlWave XFC

Service / 3-7

COM1: From the factory, RS-232 Communications Port COM1 defaults to 115.2 kbd (RS-

232) using the BSAP Protocol. Note: Port COM1 will be configured for RS-232 op-
eration (at 9600 baud) by setting CPU Switches SW1-3 and SW1-8 OFF. This will
prevent the boot project from running and places the unit into diagnostic mode.
CPU Board Switch SW1-8 must be set OFF to run the WINDIAG program.
Connec-
tion to a PC requires the use of a three-wire cable (see Figure 2-11 or 2-12).

Communication Port COM1 is located on the Terminal Plate assembly and is la-
beled the LOCAL Port; it has three terminals as follows:

J2-5 = RXD
J2-6 = TXD
J2-7 = Ground (G)

COM2: From the factory, RS-232 Communications Port COM2 defaults to 9600 baud, 8-

bits, no parity, 1 stop bit, BSAP/ControlWave Designer protocol operation (RS-
232). Note: Port COM1 will be configured for RS-232 operation (115.2 kbd) by set-
ting CPU Switches SW1-OFF. CPU/System Controller Board Switch SW1-8 must
be set OFF to run the WINDIAG program.
Connection to a PC requires the use of
an RS-232 “Null Modem” cable (see Figure 2-9).

Communication Port COM2 is located on the Terminal Plate assembly and is la-
beled the NETWORK Port; it has seven terminals as follows:


J2-8

=

TXD

J2-9

=

RXD

J2-10

=

RTS

J2-11

=

CTS

J2-12

=

DTR

J2-13

=

DCD

J2-14

=

Ground

(G)


COM3: RS-485 Communications Port COM3 defaults to 9600 baud, 8-bits, no parity, 1 stop

bit, BSAP/ControlWave Designer protocol operation. In lieu of the use of an RS-
232 Port, an RS-485 cable (see Tables 2-3 & 2-5) can be connected between COM3
and a PC’s RS-485 Port.


RS-485 Communication Port COM3 is located on the Terminal Plate assembly and

has four terminals as follows:


J2-1

=

Ground

(G)

J2-2

=

TR-

J2-3

=

TR+

J2-4

=

+V


To use the WINDIAG program place any critical process (associated with the Control-
Wave XFC unit in question) under manual control. WINDIAG cannot be run while the
ControlWave XFC application is running. Set CPU Board Switch SW1-8 to the OFF
position. Perform steps 1 through 6 below.

1. Start the OpenBSI NetView Program. A menu similar to Figure 3-3 will appear.