5 terminal plate – Emerson Process Management ControlWave XFC User Manual

Page 25

Advertising
background image

CI-ControlWave XFC

Introduction / 1-11

Table 1-3 - I/O Board Connector Summary

Ref. # Pins

Function

Notes

J2

14-pin

Comm. Port Interface

To/From Term. Block J2 on Term. Plate

J3

3-pin

RTD Interface.

From Term Block J3 on Term. Plate

J4 11-pin

AI/AO

Interface

To/From

Term. Block J4 on Term Plate

J5 12-pin

DI/DO/HSC

Interface

To/From Term. Block J5 on Term Plate

J6

2-pin

Primary Power

From Term. Block J6 on Term. Plate

J7 26-pin

CPU/SPI/Power

Interface

To/From CPU Board Connector P2

P1

8-pin

MVT or GPT Transducer Interface

To/From MVT/GPT Transducer

J7

MVT/GPT

Intf.

1

2

P1

J3

J2

J4

J6

J5

F1 = .375

Amp

1

J8

1

J1

Figure 1-5 - ControlWave XFC I/O Board

Note: J1 and J8 are for Factory Use ONLY!

1.3.5 Terminal Plate

Input/Output, Communications, Input Power and RTD wiring are connected to the
Terminal Plate; accessed by removing the Rear/Wiring Cover.

1.3.5.1 Field I/O Wiring

Field I/O Wiring is supported by Connectors on the Terminal Plate Assembly as follows:

Non-isolated Analog Input/Output Connector J4 (Section 1.3.5.1.1)
Non-isolated Digital Input/Output Connector J5 (Section 1.3.5.1.2)
Non-isolated High Speed Counter Input Connector J5 (Section 1.3.5.1.3)
Optional RTD Input Connector J3 (Section 1.3.5.1.4)

1.3.5.1.1 Non-isolated Analog I/O
(also see Sections 2.3.4.5 through 2.3.4.6.1)

Terninal Plate Term. Block connector J4 provides interface to three single ended Analog
Inputs and 1 Analog Output (respectively). Three field terminals (on J4) are assigned for

Advertising