Specifications / 4-3

4.4.3 Non-isolated Digital Input/Output Circuitry Specs.


Non-isolated Digital Inputs

Number of Inputs:

2 DI - Internally Sourced (Dry Contact) operation


Input Filtering:

15 milliseconds


Input Current:

60uA nominal


‘0’ State Voltage:

below 1.5V


‘1’ State Voltage:

above 1.5V


Electrical Isolation:

None


Surge Suppression:

Transorb between signal and ground (Meets ANSI/IEEE
C37.90-1978)

Non-isolated Digital Outputs


Number of Outputs:

4 DO


Output Configuration:

Open Drain (Externally Powered)


Maximum Load Current:

400mA each @ 30Vdc


Electrical Isolation:

None


Surge Suppression:

Transorb between signal and ground (Meets ANSI/IEEE
C37.90-1978)

General DI/DO Circuitry Specs.


Terminations:

Pluggable, max wire size is 14 gauge for local terminations -
Two 14-pin mass termination headers are provided for
remote terminations.

4.4.4 Non-isolated Analog Input/Output Circuitry Specs.


Non-isolated Analog Inputs


Number of Inputs:

3 Single Ended Inputs (1-5V)


Input Type:

(Externally Powered) Voltage Input: 1-5 Vdc


Input Impedance:

1 Meg ohm

Non-isolated Analog Outputs


Number of Outputs:

1 AO (4-20mA Sink)