Emerson Process Management ControlWave XFC User Manual

Page 60

Advertising
background image

2-18 / Installation & Operation

CI-ControlWave XFC

Table 2-2B - RS-232 Ports (COM2) Terminal Plate Connector J2 Pin Assignments

Pin

#

Signal

RS-232

Description:

RS-232 Signals

8

TXD

Transmit Data Output

9

RXD

Receive Data Input

10

RTS

Request To Send Output

11

CTS

Clear To Send Input

12

DTR

Data Terminal Ready Output

13

DCD

Data Carrier Detect Input

14 GND Power

Ground

Table 2-2C - RS-485 Port (COM3) Terminal Plate Connector J2 Pin Assignments

Pin

#

Signal

RS-485

Description:

RS-485 Signals

1

GND

Power Ground

2

TR

− Transmit/Receive

Data

−I/O

3

TR+

Transmit/Receive Data + I/O


RS-485 Ports
Control
Wave XFC can use an RS-485 communication port for local network com-
munications to multiple nodes up to 4000 feet away. Since this interface is intended for
network communications, Table 2-3 provides the appropriate connections for wiring the
master, 1st slave, and nth slave. The master node should be wired to one end of the RS-485
cable run. A 24-gauge paired conductor cable, such as Belden 9843 should be used. Note:
Only half-duplex RS-485 networks are supported.


Table 2-2C provides connector pin assignments for Comm. Port COM3.

Table 2-3 - RS-485 Network Connections

(see Table 2-2C ControlWave XFC RS-485 Port Pin # Assignments)

From

Master

To 1st

Slave

To nth

Slave

TR+ TR+ TR+

TR

− TR− TR−

GND GND GND

Note: When wiring to four-wire RS-485 Ports connect TR+ to TXD+ & RXD+
and connect TR- to TXD- and RXD-.

Note: Pins 1, 2, 3, 4 & 9 of BBI Series 3305, 3310, 3330, 3335 & 3340 RTU/DPC
RS-485 Comm. Ports are assigned as follows: 1 = TXD+, 2 = TXD-, 3 = RXD+, 4
= RXD- & 9 = ISOGND.

2.3.3 I/O Wiring


ControlWave XFCs are provided with Card Edge Terminal Blocks that accommodate field
wiring. Wiring is routed into the enclosure through a ¾” Conduit Fitting.

2.3.3.1 I/O Wire Connections


ControlWave XFC electronic flow computers utilize Terminal Blocks equipped with
compression-type terminals that accommodate up to #14 AWG wire. A connection is made

Advertising