CI-ControlWave XFC

Introduction / 1-17

• Accumulated

Energy

• Average Static Pressure
• Average

Temperature

• Average Differential Pressure
• Average Specific Gravity
• Average Heating Value
• Flow

Time

• Uncorrected

Count

Each log entry also contains the date and time. The ControlWave XFC has a Hourly
Historical Log for each of two runs.

1.5.3.2 Daily Historical Data Log


The Daily Data Log holds one record for every contract day. The contract hour may be
changed by the user. The daily log holds 62 entries; this ensures that the previous calendar
month of daily data is always resident in ControlWave XFC FLASH memory.

The following items are stored in the Daily Data Log.

• Corrected

Volume

• Uncorrected

Volume

• Accumulated

Energy

• Average Static Pressure
• Average

Temperature

• Average Differential Pressure
• Average Specific Gravity
• Average Heating Value
• Flow

Time

• Uncorrected

Count


Each log entry also contains the date and time. The ControlWave XFC has a Daily
Historical Log for each of the two runs.

1.5.3.3 Periodic Historical Data Log


The periodic data log holds one record for every log interval. Log interval is 15 minutes. The
Periodic Historical Data Log holds 1440 records, or four days of 15 minute data.

The following items are stored in the Periodic Historical Data Log:

• Flowing Differential Pressure
• Flowing Static Pressure
• Flowing

Temperature

• Frequency


Each log entry also contains the date and time. The ControlWave XFC has a Periodic
Historical Data Log for each of four runs.

1.5.3.4 Alarm and Event Storage


The ControlWave XFC keeps an Audit Trail Buffer capable of storing the most recent 500
Alarms and the most recent 500 Events. Internally, these buffers are maintained