6 configure prolink ii connection parameters, See section 2.6) – Emerson Network Router User Manual

Page 24

Advertising
background image

18

ProLink

®

II Software for Micro Motion

®

Transmitters

Installation and Setup

Figure 2-12

Modbus/RS-485 connection to RS-485 terminals on MVD Direct Connect I.S. barrier

2.6

Configure ProLink II connection parameters

To connect to the transmitter, ProLink II must use connection parameters appropriate to the
transmitter.

•

If you are connecting to an MVD Direct Connect system, ProLink II can use any of the
supported communication settings listed in Table 2-2. The core processor auto-detects
incoming communications parameters and switches to match.

•

If you are connecting to a Model 2400S transmitter using the service port:

-

For point-to-point connections, you can use a service port connection type.

-

For multidrop network connections, you can use any Modbus/RS-485 connection type and
specify the transmitter’s Modbus address. The transmitter auto-detects incoming
communications parameters and switches to match. The service port auto-detection limits
are described in Table 2-3.

•

If you use a service port or HART/Bell 202 connection type, the connection parameters are
standard: when one of these connection types is specified, ProLink II automatically uses the
appropriate parameters.

RS-485 to RS-232
signal converter

Attach serial port or USB
adapter if necessary

RS-485/B

RS-485/A

I.S. barrier

Non-I.S. terminals

Notes:
• Ensure that no other Modbus master devices are currently active on the network.
• Before using ProLink II to communicate with the core processor, disconnect any wiring to a remote PLC.