B.5 performing batch aoc calibration – Emerson Network Router User Manual

Page 90

Advertising
background image

84

ProLink

®

II Software for Micro Motion

®

Transmitters

Configuring the Discrete Batch Application

Batch management functions are shown at the top of the window:

To specify the preset to use for batching, select it from the dropdown list at the top of the
Batcher Control window, and click

Apply

.

The current target is displayed. Depending on the setting of

Lockout target

, you may or may

not be able to change the value from this screen. To change it, enter the new target value and
click

Apply

.

To inhibit batch, inhibit batch totalizer, or inhibit batch flow, select the appropriate checkboxes
and click

Apply

. For a discussion of these functions, see the preceding section.

To reset, start, stop, resume, and end a batch, use the batch control buttons. These functions
may also be assigned to a discrete event or discrete input (see Section B.3.4). For a definition
of these functions, see Table B-4.

Status of the batch application is shown at the bottom of the window. A red light indicates that the
associated condition is active.

B.5

Performing Batch AOC calibration

Batch AOC (Automatic Overshoot Compensation) keeps the actual quantity delivered as close as
possible to the batch target, by minimizing the amount of overshoot.

If batch AOC is enabled (see Section B.3.2), batch AOC calibration is required to provide data for the
compensation process. Thereafter, batch AOC calibration is recommended:

Whenever consistent overshooting or undershooting of the target occurs

If equipment (valve or pump) is changed

Note: If batch AOC is not enabled, you cannot perform batch AOC calibration.

To perform batch AOC calibration using ProLink II:

1. Choose

ProLink > Calibration > AOC Calibration

.

2. Click

Start Calibration

. The

AOC Calibration Active

light turns red, and will remain red

while batch AOC calibration is in progress.

3. Run 2–10 batches.

4. When overshoot has been adequately minimized, click

Save Calibration

.