Tab (see figure b-1) – Emerson Network Router User Manual

Page 80

Advertising
background image

74

ProLink

®

II Software for Micro Motion

®

Transmitters

Configuring the Discrete Batch Application

Figure B-1

Discrete batch configuration panel

3. Click the

Discrete Output

tab (see Figure B-2).

a.

Configure the required discrete outputs.

-

For 1-stage operation, you must configure one discrete output. This output must
control either the pump or the primary valve, as appropriate to your application. This
discrete output is required.

-

For 2-stage operation, you must configure either two or three discrete outputs: one to
control the primary valve (required), one to control the secondary valve (required),
and one to control the pump (optional; only if required by your installation).

You must configure the discrete outputs that are listed as required, whether or not your
installation uses them (for example, you may start and stop the pump manually). You will
not be able to start a batch until the required discrete outputs have been configured.

b.

Click

Apply

.