B.3.4 batch control methods – Emerson Network Router User Manual

Page 86

Advertising
background image

80

ProLink

®

II Software for Micro Motion

®

Transmitters

Configuring the Discrete Batch Application

B.3.4

Batch control methods

Batch control functions can be performed in three ways:

•

By using the function buttons on the transmitter display (see the Series 3000 transmitter
manual), or in the ProLink II

Run Batcher

window (see Section B.4)

•

By assigning a discrete input to a batch control function

•

By assigning a discrete event to a batch control function

If a discrete input or discrete event is assigned to a batch control function, the function is triggered
when the discrete input or discrete event is in an On state.

Table B-4 lists the batch control functions. To assign a discrete input or discrete event to trigger a
batch function:

1. Choose

ProLink > Configuration

and click the

Discrete Input

tab. See Figure B-3.

2. Select the batch function to be triggered. Batch functions are listed and defined in Table B-4.

3. Specify the method which will be used to trigger the batch function: Discrete Event 1–5 or

Discrete Input 1–2.

Note: You can assign one or more actions to a single discrete input or discrete event. All assigned
actions will be performed, as allowed by the configuration and current state of the discrete batch
application.

Example 2

Configure presets by percent of target under the following conditions:

•

The target is 200 kilograms

•

The primary valve opens at the start of the batch and closes when
180 kilograms have been delivered

•

The secondary valve opens when 100 kilograms have been
delivered

•

The end warning occurs when 160 kilograms have been delivered

0.90

Since 0.90 equals 90%, enter a close primary value of 90.

0.50

Since 0.50 equals 50%, enter an open secondary value of 50.

0.80

Since 0.80 equals 80%, enter an end warning value of 80.

Close primary

180 kilograms
200 kilograms

-------------------------------------

=

=

Open secondary

100 kilograms
200 kilograms

-------------------------------------

=

=

End warning

160 kilograms
200 kilograms

-------------------------------------

=

=

Advertising