76

ProLink

®

II Software for Micro Motion

®

Transmitters

Configuring the Discrete Batch Application

B.3.1

Flow source

The flow source specifies the flow variable that will be used for batch measurement. Select one of the
flow sources defined in Table B-1.

B.3.2

Control options

The batch control options are used to manage the batch process. Control options are listed and defined
in Table B-2.

Note: Control options apply to all batch presets.

Table B-1

Flow sources

Flow source

Description

None

• Batch controller is disabled.
• START button will not appear on display.

Frequency input

• Frequency input from a Micro Motion IFT9701 or RFT9739 transmitter
• Frequency input from a pulse output device

Mass flow rate

Mass flow rate from Series 3000 transmitter

Volume flow rate

Volume flow rate from Series 3000 transmitter

CM std vol flow rate

• Standard volume flow rate at reference temperature
• Standard volume flow is available only if the concentration measurement

application software is installed and configured to indicate standard volume
flow.

CM mass flow rate

• Net mass flow rate
• Net mass flow is available only if the concentration measurement application

software is installed and configured to indicate net mass flow.

CM vol flow rate

• Net volume flow rate at reference temperature
• Net volume flow is available only if the concentration measurement application

software is installed and configured to indicate net volume flow.

API temperature-corrected
volume flow

• Volume flow adjusted by the calculated volume correction factor
• Available only if the petroleum measurement application is installed and

enabled.

Table B-2

Control options

Setting

Default

Description

Enable
batch

Yes

• Select Yes to enable the discrete batch application.
• Select No to disable the discrete batch application. The operation mode will

default to the process monitor.

Count up

Yes

• If set to Yes, the total displayed on screen increases from zero to the target

value.

• If set to No, the total displayed on screen decreases from the target value to

zero

• The setting of the Count up control option affects only the quantity displayed

on screen. It does not affect configuration of presets.

• If the custody transfer application is installed, Count up is set to Yes and

cannot be changed.

Enable AOC

Yes

• Select Yes to enable Automatic Overshoot Compensation (AOC).
• When batch AOC is enabled and batch AOC calibration has been performed,

the batch controller compensates for the time required to close the valve.

• If Enable AOC is set to Yes, batch AOC calibration is required to provide data

for the compensation process. To perform batch AOC calibration, see
Section B.5.