Activation 2, Sensors config – Riello UPS NetMan 204 User Manual

Page 28

Advertising
background image

Activation 2

/------------------------/
/ Activation 2 /
/------------------------/


Enable Serial N:[

ON

/off]<--


Enable Sensors.:[

ON

/off]


Enable WOL :[on/

OFF

]

With this menu the services implemented in NetMan 204 can be activated or deactivated:

Use the ENTER key to change the selected configuration (“ON” or “OFF”).

ON (green characters): service active

OFF (red characters): service not active

It is recommended to activate only the services used.

The "Serial N" activates a virtual serial communication over network. This option must be

enabled for downloading the UPS history log file using the dedicated software.

Sensors Config

To enter on the “Sensors config” menu is necessary to enable the “Sensors” service

(Activation 2 menu) and to save the configuration (Save and load menu).

Sensor list







Press [C] to change sensors, [E] to exit

Enter on the “Config sensor” menu, connect the first sensor and press “C”. After some instants the

device will be recognized and the device will be given an identifier number [1]. Connect the next

sensor, if present, and press “N”. After some instants the device will be recognized and the device

will be given an identifier number [2]. Repeat the procedure for all the sensors and when the

configuration is finalized press “Y”.

Sensor list
1) Temperature [F100000013BE0628]

2) Humidity & Temperature [4D00000083FF3326]
3) Digital I/O & Temperature [BB0000003BA2FF12] [510000009A154228]





Press [Y] to confirm, [N] to insert a new sensor

For proper working of the devices, it is necessary to add just one device for each iteration

and wait that it is recognized by NetMan 204.

- 28 -