Reset button, Users – Riello UPS NetMan 204 User Manual
Page 8
Reset button
The reset button allows to restart the NetMan204 or to load a default configuration with a
predefined static IP address.
To reset NetMan204: keep press the reset button until the red led start flashing (ca. 2 seconds)
and then release it.
To load a configuration with predefined static IP address: keep press the reset button; first the
led starts flashing, then turns to solid red (ca. 10 seconds). When the led is solid red, release the
reset button and the NetMan 204 will reboot with:
•
IP address: 192.168.0.204
•
Netmask: 255.255.0.0
•
SSH service enabled
•
HTTP service enabled
HTTP and SSH service are enabled temporarily without changing the configuration saved
in non-volatile memory.
U
SERS
It is possible to access to NetMan 204 with three different users (admin / fwupgrade / user).
Username
Default password
Privileges
admin
admin
user with right to modify the configuration
fwupgrade
fwupgrade
user with right to upgrade the firmware
user
user
user with right to read and download the log files
- 8 -