Riello UPS NetMan 204 User Manual

Page 46

Advertising
background image

Events

Meaning

UPS Lock

UPS is locked

Ovrload/Ovrtemp

UPS in overload or in overtemperature

UPS Failure

Failure of the UPS

On bypass

Operation from bypass

Battery work

Operation from battery

Battery low

Battery low

Communic lost

Communication between the UPS and the device has been interrupted

SENTR level 2

Presence of an internal UPS failure (this condition emulates the level

of modem alarm for UPSs with PRTK code SENTR…).

SENTR level 3

Presence of a failure in the UPS, excluding those envisaged in the

previous point (this condition emulates the level of modem alarm for

UPSs with PRTK code SENTR…).

Connect the modem to the SERIAL port of NetMan 204 according to the tables below.

RJ-12 – SERIAL port

POSITION

DESCRIPTION

1

+5V

DC

2

GND

3

Environmental sensors bus

4

GND

5

RXD

6

TXD

NetMan 204

Modem

RJ-12

DB-25

DB-9

DESCRIPTION

POSITION DESCRIPTION

POSITION POSITION

1

+5V

DC

LEAVE UNCONNECTED

2

GND

3

Environmental

sensors bus

4

GND

CONNECT TO

7

5

GND

5

RXD

CONNECT TO

3

2

TXD

6

TXD

CONNECT TO

2

3

RXD

- 46 -