Bacnet/ip configuration – Riello UPS NetMan 204 User Manual
Page 43
BACNET/IP CONFIGURATION
For BACnet/IP configuration, you have to set the following variables using "Expert mode":
set bacnet_enable <true/false> true → to enable the service
false → to disable the service
set bacnet_address <your Instance Device address> default value → 1968
set bacnet_client <IP address of your BACnet client>
For example, if the IP address of your BACnet client is 10.1.10.1 and you want to enable the
BACnet/IP on your NetMan 204, you have to enter in expert mode and type the following
commands:
Netman mainteinance console
Available commands:
help prints this help
get shows all values
set <VAR> <VALUE> set VAR to VALUE
delete <VAR> removes VAR
sendtrap <TRAPCODE> send a test SNMP trap
reboot reboot the NetMan
factoryreset restore factory configuration
erasefram erase the FRAM module
exit closes the connection
netman>
set bacnet_enable true
netman>
set bacnet_client 10.1.10.1
- 43 -