BACNET/IP CONFIGURATION

For BACnet/IP configuration, you have to set the following variables using "Expert mode":

set bacnet_enable <true/false> true → to enable the service

false → to disable the service

set bacnet_address <your Instance Device address> default value → 1968

set bacnet_client <IP address of your BACnet client>

For example, if the IP address of your BACnet client is 10.1.10.1 and you want to enable the

BACnet/IP on your NetMan 204, you have to enter in expert mode and type the following

commands:


Netman mainteinance console
Available commands:
help prints this help
get shows all values
set <VAR> <VALUE> set VAR to VALUE
delete <VAR> removes VAR
sendtrap <TRAPCODE> send a test SNMP trap
reboot reboot the NetMan
factoryreset restore factory configuration
erasefram erase the FRAM module
exit closes the connection

netman>

set bacnet_enable true

netman>

set bacnet_client 10.1.10.1