Riello UPS NetMan 204 User Manual

Page 41

Advertising
background image

REGISTER

(1)

UPS – NOMINAL DATA

UNIT

NUMBER ADDRESS

73ч77

72ч76

78

77

Output nominal voltage (star)

V

79

78

Output nominal frequency

0.1*Hz

80

79

Output nominal power

100*VA

81ч83

80ч82

84

83

Battery nominal capacity (battery expansion included)

Ah

85

84

Battery benches

(1 or 2)

86

85

Battery type

Integer

87ч112

86ч111

REGISTER

(1)

UPS - COMMANDS

UNIT

NUMBER ADDRESS

113

112

Command code

(2)

Integer

114

113

Shutdown delay time

Seconds

115

114

Restore delay time

Minutes

116

115

117

116

Command result

(3)

Integer

118

117

REGISTER

(1)

DIAGNOSTIC

UNIT

NUMBER ADDRESS

119

118

Counter of processed correct messages

Integer

120

119

Counter of processed NOT correct messages

Integer

(1)

The register number

n must be addressed n-1 in the data packet.

(2)

Refer to “Command codes” paragraph

(3)

Command result = Command code if command is handled from the UPS

Command result = Command code + 100 if command is NOT handled from the UPS
Command result = 0 if Command code is wrong

- 41 -