Riello UPS NetMan 204 User Manual
Page 41
REGISTER
(1)
UPS – NOMINAL DATA
UNIT
NUMBER ADDRESS
73ч77
72ч76
78
77
Output nominal voltage (star)
V
79
78
Output nominal frequency
0.1*Hz
80
79
Output nominal power
100*VA
81ч83
80ч82
84
83
Battery nominal capacity (battery expansion included)
Ah
85
84
Battery benches
(1 or 2)
86
85
Battery type
Integer
87ч112
86ч111
REGISTER
(1)
UPS - COMMANDS
UNIT
NUMBER ADDRESS
113
112
Command code
(2)
Integer
114
113
Shutdown delay time
Seconds
115
114
Restore delay time
Minutes
116
115
117
116
Command result
(3)
Integer
118
117
REGISTER
(1)
DIAGNOSTIC
UNIT
NUMBER ADDRESS
119
118
Counter of processed correct messages
Integer
120
119
Counter of processed NOT correct messages
Integer
(1)
The register number
n must be addressed n-1 in the data packet.
(2)
Refer to “Command codes” paragraph
(3)
Command result = Command code if command is handled from the UPS
Command result = Command code + 100 if command is NOT handled from the UPS
Command result = 0 if Command code is wrong