I/O Sensors

/------------------------/
/ Output /
/------------------------/

Output

UPS Lock.......: -<--

Ovrload/Ovrtemp: -

UPS Failure....: -

On bypass......: -

AC Fail........: 3

Battery low....: -

Communic lost..: -

Input sensor...: -NC

Press [Esc] to quit

With this menu is possibile to associate a digital output of the installed sensors to one or more

events of the UPS. The output will be closed when the associated event happens.

Press ENTER to select the output.

The identification number is the same which is associated to the sensor during

installation.

The following table describes the meaning of the events. These can vary depending on the UPS

connected.

Event

Description

UPS Lock

UPS is locked

Ovrload/Ovrtemp

UPS in overload or in overtemperature

UPS Failure

Failure of the UPS

On bypass

Operation from bypass

AC Fail

Operation from battery

Battery low

Battery low

Communic lost

Communication between the UPS and the device has been interrupted

Input Sensor

The state of the input (open/closed) is reported to the output of the

selected sensor.

The digital input monitored is that with the lowest identification number

(the first that was detected during configuration).

It is also possible to select the logic state of the input:

NC: Normally Closed

NO: Normally Open