Riello UPS NetMan 204 User Manual
Page 29
Example: how to connect a Temperature sensor, a Humidity & Temperature sensor and a Digital
I/O & Temperature sensor in exactly this order.
Sensor list
Press [C] to change sensors, [E] to exit
Connect the first sensor (Temperature), and press “C”.
Sensor list
1) Temperature [F100000013BE0628]
Press [Y] to confirm, [N] to insert a new sensor
Wait until the first sensor is identified and then connect the second sensor (Humidity &
Temperature), and press “N”.
Sensor list
1) Temperature [F100000013BE0628]
2) Humidity & Temperature [4D00000083FF3326]
Press [Y] to confirm, [N] to insert a new sensor
Wait until the second sensor is identified and then connect the third sensor (Digital I/O &
Temperature), and press “N”.
Sensor list
1) Temperature [F100000013BE0628]
2) Humidity & Temperature [4D00000083FF3326]
3) Digital I/O & Temperature [BB0000003BA2FF12] [510000009A154228]
Press [Y] to confirm, [N] to insert a new sensor
Press “Y” to confirm.
- 29 -