Example: how to connect a Temperature sensor, a Humidity & Temperature sensor and a Digital

I/O & Temperature sensor in exactly this order.

Sensor list







Press [C] to change sensors, [E] to exit

Connect the first sensor (Temperature), and press “C”.

Sensor list

1) Temperature [F100000013BE0628]





Press [Y] to confirm, [N] to insert a new sensor

Wait until the first sensor is identified and then connect the second sensor (Humidity &

Temperature), and press “N”.

Sensor list

1) Temperature [F100000013BE0628]
2) Humidity & Temperature [4D00000083FF3326]





Press [Y] to confirm, [N] to insert a new sensor

Wait until the second sensor is identified and then connect the third sensor (Digital I/O &

Temperature), and press “N”.

Sensor list
1) Temperature [F100000013BE0628]
2) Humidity & Temperature [4D00000083FF3326]

3) Digital I/O & Temperature [BB0000003BA2FF12] [510000009A154228]




Press [Y] to confirm, [N] to insert a new sensor

Press “Y” to confirm.