Modem configuration – Riello UPS NetMan 204 User Manual

Page 45

Advertising
background image

MODEM CONFIGURATION

NetMan 204 can be used to monitor the status of the UPS by means of a modem connected to the

SERIAL port.

The modem parameters can be configured only via HTTP.

The modem can be enabled for transmission and/or for receiving calls.

If the transmission is enabled, the UPS is able to make calls to a remote support station to notify

any alarm situations. The device can make calls to three different telephone numbers.

If the modem is enabled to receive calls, it is possible to monitor the UPS status and operation

from a remote support station.

Field

Parameters to be inserted

Phone number 1

Enter the telephone numbers to be called

Phone number 2
Phone number 3
Modem init

Enter the modem initialization string (see note)

Modem dial

Enter the dialling string used by the modem (see note)

No. Repeat

Enter the number of attempts to be made if there is no reply

Delay

Enter the interval of time between two calls if there is no reply

The modem initialization string (Modem init) recommended for the U.S. Robotics modem

is

ATE0X0V0&H0&R1&I0&D0S0=1&W0 (default configuration).

The dialling string (Modem dial) recommended for the U.S. Robotics modem is

ATDT

(default configuration).

It's also possible to establish which telephone numbers will be called and with which mode when

certain events occur. One or more telephone numbers can be associated with each event.

The tables below describe the meaning of the events. These can vary according to the UPS

connected.

Select AND if you want that when the event occurs, all the enabled telephone numbers will be

called.

Select OR if you want that when the event occurs, only one of the enabled telephone numbers is

called: if all the call attempts for the first enabled telephone number fail, the device calls the next

enabled telephone number.

- 45 -

Advertising