Technical data – Amprobe Telaris-ISO-PRO Insulation-Tester User Manual

Page 29

Advertising
background image

Technical Data

Insulation Resistance Measurement
Measurement Range

Resolution

Tolerance

0,010...1,999 M

Ω

1 k

Ω

±(5% rdg. +10 Digits)

2,00...19,99 M

Ω

10 k

Ω

±(5% rdg. +5 Digits)

20,0...199,9 M

Ω

100 k

Ω

±(5% rdg. +5 Digits)

0,200...1,999 G

Ω

1 M

Ω

±(10% rdg. +5 Digits)

Battery Life
Nominal test

number of measurements with 1mA - Load

Voltage UN

(1 measurement - 25 s pause)

100 V DC

approx. 6000

250 V DC

approx. 4000

500 V DC

approx. 3000

1000 V DC

approx. 1000

Max. open voltage Uo UN +25%

Test current IN:

≥ 1 mA at UN

Short-circuit current IK:

< 2 mA

Measurement duration:

1 - 3 s

(automatic function)

1 - 10 s

(automatic function for capacitance loads)

optional

(continuous measurement)

10 s, 30 s, 180 s

(Timer mode)

Overload protection:

1200 V AC/DC

Automatic measurement range selection. UUT is automatically discharged after the
measurement.

Low Ohm Measurement (Low

Ω)

Measurement Range

Resolution

Tolerance

0,03...19,99

Ω

0,01

Ω

±(3% rdg. +3 Digits)

Open voltage Uo:

5 V...9 V DC

Measurement current:

≥ 200 mA (at resistance ≤ 4 Ω)

Measurement duration:

approx. 1 s

Number of measurements:

approx. 3000 (for 1

Ω, 1 measurement - 25 s pause)

Test Lead Compensation
Up to test lead resistance:

max. 1,99

Ω

Overload protection:

1200 V AC/DC, as from 600 V AC/DC the internal fuse
trips.

27

PAEB30872322:Layout 1 02.10.2008 15:57 Uhr Seite 27