Communication error codes – ProSoft Technology MVI69L-MBTCP User Manual

Page 103

Advertising
background image

MVI69L-MBTCP ♦ CompactLogix Platform

Diagnostics and Troubleshooting

Communication Module

User Manual

ProSoft Technology, Inc.

Page 103 of 152

January 6, 2014

6.5

Communication Error Codes

Standard Modbus Protocol Exception Code Errors

Code

Description

1

Illegal Function Code

2

Illegal Data Address

3

Illegal Data Value

4

Failure in Associated Device

5

Acknowledge

6

Busy, Rejected Message

Module Communication Error Codes

Code

Description

-1

CTS modem control line not set before transmit

-2

Timeout while transmitting message

-11

Timeout waiting for response after request

253

Incorrect slave address in response

254

Incorrect function code in response

255

Invalid CRC/LRC value in response

Command List Entry Errors

Code

Description

-41

Invalid enable code

-42

Internal address > maximum address

-43

Invalid node address (< 0 or > 255)

-44

Count parameter set to 0

-45

Invalid function code

-46

Invalid swap code

MBTCP Client-Specific Errors

Code

Description

-33

Failed to connect to server specified in command

-36

MBTCP command response timeout

-37

TCP/IP connection ended before session finished

Note: If an error code is reported that is not listed above, check with the documentation of the end
device. Device-specific error codes can be produced by the end device.