3.2.3 MBTCP Client x

This section defines the general configuration for MBTCP Client x. Up to 10
MBTCP Clients can be configured, each using the parameters below.

Parameter

Value

Description

Enabled

Yes or No

Enables this client

Start Active

Yes or No

Specifies whether to start with commands active on boot up

Error/Status Pointer

-1 to 239

Specifies the starting register location in

the module’s

database for the error/status table for this client. If a value
of -1 is entered, the error/status data will not be placed in
the database.

All other valid values determine the starting location of the
data. This data should be placed within the read data range
of module memory.

Command Error
Pointer

-1 to 239

Specifies the address in the

module’s database where the

command error data will be placed. If the value is set to -1,
the data will not be transferred to the database. This data
should be placed within the read data range of module
memory.

Minimum Command
Delay

0 to 65535
milliseconds

Specifies the number of milliseconds to wait between
receiving the end of a server's response to the most recently
transmitted command and the issuance of the next