ProSoft Technology MVI69L-MBTCP User Manual

Page 124

Advertising
background image

Reference

MVI69L-MBTCP ♦ CompactLogix Platform

User Manual

Communication Module

Page 124 of 152

ProSoft Technology, Inc.

January 6, 2014

Addr in Dev - same as when Float Flag: Y as long as the Server's Float Flag =
Y.

In the above example, the Client's Modbus command to transmit inside the
Modbus packet will be as follows.

Server
address

Function
Code

Address in
Device

Reg
Count

Byte
Count

Data

DEC

01

16

7100

2

4

85.37

HEX

01

10

1B BC

00 02

04

BD 71 42 AA

In this example, the Client's Modbus packet contains the data byte and data word
counts that have NOT been doubled from the amount specified by Reg Count
due to the Float Flag set to N. The Server looks for the byte count in the data
packet to know the length of the data to read from the wire. Because of
insufficient byte count, some servers will read only half the data from the Client's
transmission. Other servers will read all 8 bytes in this example because they will
know where in the packet the data starts and ignore the byte count parameter
inside the Modbus packet.

Specific Example#3: Client is issuing Modbus command with FC 3 to transfer Float data
from Server.

Float Flag: Not applicable with Modbus Function Code 3.

Float Start: Not applicable with Modbus Function Code 3.

DB Addr - Tells the Client where in its data memory to store the data obtained
from the Server.

Reg Count - Tells the Client how many registers to request from the Server.

Swap Code - same as above.