ProSoft Technology MVI69L-MBTCP User Manual

Page 125

Advertising
background image

MVI69L-MBTCP ♦ CompactLogix Platform

Reference

Communication Module

User Manual

ProSoft Technology, Inc.

Page 125 of 152

January 6, 2014

Func Code - Tells the Client to read the register values from the Server. FC3.

Addr in Dev - Tells the Client where in the Server's database to obtain the data.

In the above example, the Client's Modbus command to transmit inside the
Modbus packet will be as follows.

Server address Function Code Address in Device Reg count

DEC

01

3

6100

2

HEX

01

03

17 D4

00 02

In the above example the (Enron/Daniel supporting) Server's Modbus command
to transmit inside the Modbus packet will be as follows.

Server address Function Code Byte Count

Data

DEC

01

3

8

32.75 275.69

HEX

01

03

08

00 00 42 03 D8 52 43 89

In the above example the (a NON-Enron/Daniel supporting) Server's Modbus
command that will be transmitted inside the Modbus packet will be as follows.

Server address Function Code Byte Count

Data

DEC

01

3

4

32.75

HEX

01

03

04

00 00 42 03


Advertising