Using Controller Tags

MVI69L-MBTCP ♦ CompactLogix Platform

User Manual

Communication Module

Page 82 of 152

ProSoft Technology, Inc.

January 6, 2014

MBTCP.CONTROL.EventCommand_
DBData.SwapCode

0,1,2,3

Defines if the data received from the
Modbus server is to be ordered
differently than received from the server
device.
This parameter is helpful when dealing
with floating-point or other multi-register
values, as there is no standard method
of storage of these data types in server
devices.

MBTCP.CONTROL.EventCommand_
DBData.ModbusFC

1,2,3,4,5,6,1
5,16

Specifies the Modbus function to be
executed by the command.

MBTCP.CONTROL.EventCommand_
DBData.DeviceModbusAddress

0 to 9999

Specifies the register or digital point
address offset within the Modbus server
device. The MBTCP Client will read or
write from/to this address within the
server.

MBTCP.CONTROL.EventCommand_
DBData.StatusReturned

0, 1, or -1

0 = Fail

1 = Success

-1 = Client is not Enabled and Active

MBTCP.CONTROL.EventCommand_
DBData.CmdInQue

Number of Commands in Queue waiting
to be executed

5.3.3.3 MBTCP.CONTROL.EventCommand_PLCData

This array allows the processor to dynamically build Modbus commands with
PLC processor data. This feature is meant for periodic execution such as a clock
reset, zeroing-out counters, etc.

Tag Name

Range

Description

MBTCP.CONTROL.EventCommand_
PLCData.Trigger

0 or 1

Toggle to send Event Command.
0 = Disable, 1 = Enable

MBTCP.CONTROL.EventCommand_
PLCData.ClientID

0 to 9

Client ID associated with the command
to be executed

MBTCP.CONTROL.EventCommand_
PLCData.ServerIPaddress

xxx.xxx.xxx.
xxx

IP address of target Modbus server

MBTCP.CONTROL.EventCommand_
PLCData.ServicePort

502 or 2000

Service port of target Modbus server

MBTCP.CONTROL.EventCommand_
PLCData.SlaveAddress

1 to 255

Slave address of target Modbus TCP/IP
to serial device, for backwards
compatibility

MBTCP.CONTROL.EventCommand_
PLCData.ModbusFunctionCode

1,2,3,4,5,6,1
5,16

Specifies the Modbus function to be
executed by the command.

MBTCP.CONTROL.EventCommand_
PLCData.DeviceDBAddress

0 to 9999

Specifies the register or digital point
address offset within the Modbus server.
The MBTCP Client will read or write
from/to this address within the server.

MBTCP.CONTROL.EventCommand_
PLCData.PointCount

1 to 125
(words) or

1 to 800
(coils)

Specifies the number of registers or
digital points to be associated with the
command. Modbus Function Codes 5
and 6 ignore this field as they only apply
to a single data point.

MBTCP.CONTROL.EventCommand_
PLCData.Data

Data values associated with the
command

MBTCP.CONTROL.EventCommand_
PLCData.ErrorStatus

Command status after execution

Advertising