AN-X-AMXRIO Page

21

Input and Output Data

The tag file contains the location of the scheduled input and output data for all I/O
modules and registers. When you import the tag file into RSLogix 5000, you can use the
tags to refer to I/O data.

Refer to page 26 for detailed information on the tag file format.

Status Input Data

The status input data consists of the following diagnostic data.

Offset

Description

0

Drop status, 1 = good, 0 = bad or not present

Bit 1 = drop 1, bit 7 = drop 7, etc

1

Drop 1 extended status

0 = OK, 1 = No response, 2 = Configuration mismatch,
3=Length error, 4 = mask error

2

Drop 2 extended status

3

Drop 3 extended status

4

Drop 4 extended status

5

Drop 5 extended status

6

Drop 6 extended status

7

Drop 7 extended status

8

Transmit count

9

Receive count

10

Receive protocol errors

11

Receive noise

12

Receive timeout

13

Receive CRC error

14

Receive overrun

15

Receive abort

16

ControlLogix output average update time for previous 100
updates

17

ControlLogix output minimum update time for previous 100
updates

18

ControlLogix output maximum update time for previous 100
updates

19

ControlLogix output maximum update time since connection
opened