AN-X-AMXRIO Page

23

If the log overflows, AN-X closes the log file (enetip.0) and opens a second log file
(enetip.1) and continues to alternate between the two log files as each one fills up. Use
View All Logs to view both log files.

Using RSLogix 5000 to Diagnose Problems

You display the Module Properties dialog by right clicking on the module while online
with RSLogix 5000. This may help diagnosing some problems, especially connection
errors.

The following information is based on version 12.00 of RSLogix 5000.

General Tab

The Type should be ETHERNET MODULE Generic Ethernet Module

The Vendor should be Allen-Bradley (since it’s configured as a generic module)

The name and description are whatever you set when you configured the module.

Comm Format, IP Address and Connection Parameters should match what you set when
you configured the module.