Function mode – Hitachi SJ300 User Manual

Page 10

Advertising
background image

1- 7

Function mode

Code

Function name

SJ300 Setting range

Initial data
-FE/-FU/-F

Note

b034

RUN time/Power ON time level

0.-9999./1000-6553(10000-65530)hr

0.

b035

Operation direction restrict

00(Reverse is valid)/01(Only forward)/02(Only reverse)

00

b036

Start reduced voltage

00(Start reduced voltage time small)-06(Start reduced voltage time large)

06

b037

Display selection

00(all display)/01(each function display)/02(User setting / main setting)

00

b040

Torque limit mode selection

00(4 quadrant mode)/01(Terminal operation)/

02(Analog input)/03(Option1)/04(Option2)

00

b041

Torque limit level 1 setting
(Forward-driving at
4 quadrant mode)

0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>

150.

b042

Torque limit level 2 setting
(Reverse-regenerating at
4 quadrant mode)

0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>

150.

b043

Torque limit level 3 setting
(Reverse-driving at
4 quadrant mode)

0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>

150.

b044

Torque limit level 4 setting
(Forward-regenerating at
4 quadrant mode)

0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>

150.

b045

Torque LAD-STOP selection

00(Invalid)/01(Valid)

00

b046

Reverse run prevention
selection

00(Invalid)/01(Valid)

00

b050

Selection of non-stop
function at instantaneous
power failure

00(Invalid)/01(Valid)

00

b051

Start voltage of non-stop
function setting

0.0-1000.(V)

0.0

b052

OV LAD-STOP level of non-
stop function setting

0.0-1000.(V)

0.0

b053

Deceleration time of non-
stop function setting

0.01-99.99/100.0-999.9/1000.-3600.(s)

1.00

b054

Deceleration frequency widt h
of non-stop function setting

0.00-10.00(Hz)

0.00

b080

AM adjustment

0. - 255.

180

b081

FM adjustment

0. - 255.

60

b082

Start frequency adjustment

0.10-9.99(Hz)

0.50

b083

Carrier frequency setting

0.5-15.0(kHz) Derating enable, <0-10kHz>

5.0 <3.0>

b084

Initialize mode

00(Trip history clear)/01(Data initialization)/

02(Trip history clear + data initialization)

00

b085

Country code for initialization

00(Interior)/01(EC)/02(USA)

01/02/00

b086

Frequency scalar conversion
factor

0.1-99.9

1.0

b087

STOP key enable

00(valid)/01(invalid)

00

b088

Resume on FRS cancellation
mode

00(0Hz start)/01(Start f-equaling)

00

b090

BRD usage ratio

0.0-100.0(%)

0.0

b091

Stop mode selection

00(deceleration stop)/01(Free-run stop)

00

b092

Cooling fan control

00(Always ON)/

01(ON during run, After power ON, then for 5 minutes on stop is implied.)

00

b095

BRD selection

00(invalid)/01(valid<invalid during stop>)/02(valid<valid during stop>)

00

b096

BRD ON level

330-380/660-760(V)

360/720

b098

Thermistor selection

00(invalid)/01(Positive temperature coefficient enable)/02 (NTC enable)

00

b099

Thermistor error level

0. - 9999. ( ohm)

3000.

b120

Braking control selection

00(Invalid)/01(valid)

00

b121

Waiting time for releasing
braking conformation

0.00-5.00(s)

0.00

b122

Waiting time for acceleration

0.00-5.00(s)

0.00

b123

Waiting time for stop

0.00-5.00(s)

0.00

b124

Waiting time for signal
conformation

0.00-5.00(s)

0.00

b125

Releasing frequency

0.00-99.99/100.0-400.0(Hz)

0.00

b126

Releasing current

0.00*rated current-2.00*rated current(A)

Rated

current of

inverter

C091

Debug mode selection

00(No display)/01(Display)

00

C101

UP/DWN selection

00(No frequency data)/01(Keep frequency data)

00

C102

Reset selection

00(Trip cancel during ON)/01(Trip cancel during OFF)/

02(Valid only during trip<Cancel during ON>)

00

C103

Reset f frequency matching
selection

00(0Hz start)/01(Start f-equaling)

00

C111

Overload

advance

notice

level

0.0-2.0*rated current(A)

Inverter

rated

current

C121

O zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

C122

OI zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

C123

O2 zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

(Note) < > indicate the setting range of 75 to 150kW

The others