Code

Function name

SJ300 Setting range

Initial data
-FE/-FU/-F

Note

C011

Intelligent input 1 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C012

Intelligent input 2 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C013

Intelligent input 3 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C014

Intelligent input 4 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C015

Intelligent input 5 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C016

Intelligent input 6 a/b
(NO/NC) selection

00(NO)/01(NC)

00/01/00

C017

Intelligent input 7a/b
(NO/NC) selection

00(NO)/01(NC)

00

C018

Intelligent input 8 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C019

Input FW a/b (NO/NC)
Selection

00(NO)/01(NC)

00

C021

Intelligent output 11 setting

01

C022

Intelligent output 12 setting

00

C023

Intelligent output 13 setting

03

C024

Intelligent output 14 setting

07

C025

Intelligent output 15 setting

08

C026

Alarm relay output

00(RUN:running)/01(FA1:Frequency arrival type1 signal)/
02(FA2:over setting frequency)/03( OL:Overload advance notice signal)/
04( OD:Output deviation for PID control)/05( AL:Alarm signal)/
06(FA3:Only setting frequency)/07( OTQ:Over-torque signal)/
08( IP:On instantaneous stop)/09( UV:Under voltage)/
10(TRQ:Torque limit)/11(RNT:RUN time over/12(ONT:ON time over)/
13(THM:thermal caution)/19( BRK:Brake release signal)/
20( BER:Brake error signal)/21( ZS:Zero speed detect signal)/
22(DSE:Speed error over signal)/23( POK:Positioning completion signal)
24(FA4:Over frequency 2 signal)/25(FA5:Only setting frequency)/
26(OL2: Overload advance notice signal 2)
(Intelligent output terminal 11-13 or 11-14 becomes AC0-AC2 or AC0-AC3
(Can:Alarm cord output) forcibly when alarm cord output is selected in
C062)

05

C027

FM selection

00(Output frequency)/01(Output current) /02(Output torque)/
03(Digital output frequency)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)

00

C028

AM selection

00(Output frequency)/01(Output current)/02(Output torque)/
04(Output voltage)/05(Input electric power)/06(thermal load rate)/
07(LAD frequency)

00

C029

AMI selection

00(Output frequency)/01(Output current)/02(Output torque)/
04(Output voltage)/05(Input electric power)/
06(Thermal load rate)/07(LAD frequency)

00

C031

Intelligent output 11 a/b

00(NO)/01(NC)

00

C032

Intelligent output 12 a/b

00(NO)/01(NC)

00

C033

Intelligent output 13 a/b

00(NO)/01(NC)

00

C034

Intelligent output 14 a/b

00(NO)/01(NC)

00

C035

Intelligent output 15 a/b

00(NO)/01(NC)

00

C036

Alarm relay output a/b

00(NO)/01(NC)

01

C040

Overload advance notice
signal output mode

00(On accel. And decel, constant speed)/01(Only constant speed)

01

C041

Overload

advance

notice

level

0.0-2.0*rated current(A)

Inverter

rated current

C042

Frequency arrival setting for
acceleration.

0.00-99.99/100.0-400.0(Hz)

0.00

C043

Arrival frequency setting for
deceleration .

0.00-99.99/100.0-400.0(Hz)

0.00

C044

PID deviation setting level

0.0-100.0(%)

3.0

C045

Frequency arrival setting for
acceleration 2.

0.00-99.99/100.0-400.0(Hz)

0.00

C046

Arrival frequency setting for
deceleration 2.

0.00-99.99/100.0-400.0(Hz)

0.00

C055

Over torque level setting
(Forward-driving)

0.-200.(%) <0.-180.>

100.

C056

Over torque level setting
(Reverse-regenerating)

0.-200.(%)

100.

C057

Over torque level setting
(Reverse-driving)

0.-200.(%) <0.-180.>

100.

C058

Over torque level setting
(Forward-regenerating)

0.-200.(%) <0.-180.>

100.

C061

Thermal warning level
setting

0.-100.(%) <0.-180.>

80.

C062

Alarm code selection

00(Invalid)/01(3bit)/02(4bit)

00

C063

Zero speed detection level
setting

0.00-99.99/100.(Hz)

0.00

C070

Data command

02(operator)/03(RS485)/04(option1)/05(option2)

02

C071

Communicating transmission
speed

02(loop-back test)

03(2400bps)/04(4800bps)/05(9600bps)/06(19200bps)

04

C072

Communication code

1. - 32.

1.

C073

Communication bit

7(7bit)/8(8bit)

7

C074

Communication parity

00(no parity name)/01(even parity)/02(odd parity)

00

C075

Communication stop bit

1(bit)/2(bit)

1

C078

Communication waiting time

0.-1000.(ms)

0.

C081

O adjustment

0.-9999./1000-6553(10000-65530)

Setting on
forwarding

C082

OI adjustment

0.-9999./1000-6553(10000-65530)

Setting on
forwarding

C083

O2 adjustment

0.-9999./1000-6553(10000-65530)

Setting on
forwarding

C085

Thermistor adjustment

0.0 - 1000.

105.0

C086

AM offset adjustment

0.0 - 10.0(V)

0.0

C087

AMI adjustment

0. - 255.

80

C088

AMI offset adjustment

0. - 20.0( mA)

4.0