Function mode

Code

Function name

SJ300 Setting range

Initial data

-FE/-FU/-F

Note

b012

Electronic thermal level

0.2*constant current-1.20*constant current(A)

Rated
Current of
inverter

b212

Electronic thermal level
(2

nd

motor)

0.2*constant current-1.20*constant current(A)

Rated
Current of
Inverter

b312

Electronic thermal level
(3

rd

motor)

0.2*constant current-1.20*constant current(A)

Rated
current of
inverter

b013

1

s t

electronic thermal

characteristic selection

00(reduced characteristic)/ 01(constant torque characteristic)/

02(free setting)

01/01/00

b213

2

nd

electronic thermal

characteristic selection

00(reduced characteristic)/ 01(constant torque characteristic)/

02(free setting)

01/01/00

b313

3

rd

electronic thermal

characteristic selection

00/(reduced characteristic)01(constant torque characteristic)/

02(free setting)

01/01/00

b015

Free electronic thermal
frequency 1

0.-400.(Hz)

0.

b016

Free electronic thermal
current 1

0.0-1000.(A)

0.0

b017

Free electronic thermal
frequency 2

0.-400.(Hz)

0.

b018

Free electronic thermal
current 2

0.0-1000. (A)

0.0

b019

Free electronic thermal
frequency 3

0.-400.(Hz)

0.

b020

Free electronic thermal
current 3

0.0-1000.(A)

0.0

b021

Overload restriction selection

00(invalid)/01(enabled on acceleration / constant speed)/

02(enabled on constant speed)/03(enabled on acceleration / constant

speed (speed increasing at regenerating mode))

01

b022

Overload restriction level

0.50* rated current-2.00* rated current(A) <-1.80*ratede current(A)>

Rated current

of Inverter

x 1.50

b023

Overload restriction limit
constant

0.10-30.00(s)

1.00

b024

Overload restriction 2
selection

00(invalid)/01(enabled on acceleration / constant speed)/

02(enabled on constant speed)/03(enabled on acceleration / constant

speed (speed increasing at regenerating mode))

01

b025

Overload restriction level 2

0.50*rated current-2.00*rated current(A) <-1.80*rated current(A)>

Rated current

of inverter

x1.50

b026

Overload restriction constant
2

0.10-30.00(s)

1.00

b031

Software lock mode selection

00(impossible to change the data except this item when SFT terminal is
ON)/01(impossible to change the data except setting frequency item
when SFT terminal is ON)/02(impossible to change the data except this
item)/
03(impossible to change the data except setting frequency item)/
10(possible to change data on operating)

01

b100

Free V/f frequency 1

0.- Free V/f frequency2(Hz)

0.

b101

Free V/f voltage 1

0.-800.0(V)

0.0

b102

Free V/f frequency 2

0.- Free V/f frequency3(Hz)

0.

b103

Free V/f voltage 2

0.-800.0(V)

0.0

b104

Free V/f frequency 3

0.- Free V/f frequency4(Hz)

0.

b105

Free V/f voltage 3

0.-800.0(V)

0.0

b106

Free V/f frequency 4

0.- Free V/f frequency5(Hz)

0.

b107

Free V/f voltage 4

0.-800.0(V)

0.0

b108

Free V/f frequency 5

0.- Free V/f frequency6(Hz)

0.

b109

Free V/f voltage 5

0.-800.0(V)

0.0

b110

Free V/f frequency 6

0.- Free V/f frequency7(Hz)

0.

b111

Free V/f voltage 6

0.-800.0(V)

0.0

b112

Free V/f frequency 7

0.-400.(Hz)

0.

b113

Free V/f voltage 7

0.-800.0(V)

0.0

C001

Intelligent input 1 setting

18

C002

Intelligent input 2 setting

16

C003

Intelligent input 3 setting

06

C004

Intelligent input 4 setting

11

C005

Intelligent input 5 setting

09

C006

Intelligent input 6 setting

03/13/03

C007

Intelligent input 7 setting

02

C008

Intelligent input 8 setting

01/(RV:Reverse is valid)/02(CF1:Multi-speed1)/ 03(CF2:Multi-speed2)/

04(CF3:Multi-speed3)/ 05(CF4:Multi-speed4)/ 06(JG:Jogging)/

07( DB:External DC braking)/ 08(SET:2

nd

control)/

09(2CH:two-stage adjustable speed)/ 11( FRS:Free-run)/ 12( EXT:External trip)/

13( USP:Unattended start protection)/ 14(CS:commercial change)/

15(SFT:software lock)/ 16(AT:Analog input voltage/current select)/

17(SET3:3

rd

control)/ 18(RS:Reset inverter)/ 20(STA:3wire run)/

21(STP:3wire keep)/ 22(F/R:3wire forward/reverse)/

23(PID:PID selection valid/invalid)/ 24(PIDC:PID integrating reset)/

26( CAS:Control gain switch function)/ 27( UP:Remote control UP function)/

28( DWN:Remote control DOWN function)/29( UDC:Remote control data clear)/

31( OPE:Operating by operator select)/ 32(SF1:Multi-speed bit1)/

33(SF2:Multi-speed bit2)/ 34(SF3:Multi-speed bit3)/ 35(SF4:Multi-speed bit4)/

36(SF5:Multi speed bit5)/ 37(SF6:Multi-speed bit6)/ 38(SF7:Multi-speed bit7)/

39( OLR:Overload restriction change) / 40(TL:Torque limit select)/

41(TRQ1:Torque limit switch 1)/ 42(TRQ2:Torque limit switch 2)/

43((PPI:P/PI switch)/ 44(BOK:Braking comformation)/ 45( ORT:Orientation)/

46(LAC:LAD cancel)/ 47(PCLR:Position error clear)/

48(STAT:Permission of pulse train)/ no(NO:No assign)

01

(Note) < > indicate the setting range of 75 to 150kW









Electronic thermal

Free V/f setting

Intelligent input terminal setting

Overload limit