4. The check of control power supply voltage and a control signal

4.1 Control power supply

Measurement place

Item

Tolerance level

+

-

PV5 +5V power supply

4.5V - 5.5V

J1 connector 25,16pin

Control terminal L

PV12 +12V power supply

10.8V - 13.2V

J1 connector 7pin

Control terminal L

NV12 -12V power supply

-13.2V - -10.8V

J1 connector 5pin

Control terminal L

PV24 24V power supply

21.6V - 26.4V

J1 connector 3,4pin,

Control terminal P24

Control terminal CM1

4.2 Control signal

Signal

Measurement place

The contents of operation

Observation waveform

VDC

J1 connector 12pin-L

A main circuit direct-current voltage
detected signal
VDC=6.396V/400V*VPN(200Vclass)
VDC=6.396V/800V*VPN(400Vclass)

Direct-current voltage

IUF
IWF

J1 connector 9pin-L
J1 connector 8pin-L

A motor current detected signal
At the time of inverter rated load: About
3.3 V peak

TRIP

J1 connector 21pin-L

The signal at the time of carrying out a
trip by the trip factor which a gate array
judges (P3-1 reference)
Normal : 5V(H)
Inside of a trip : about 0.3V(L)

Direct-current voltage

PHF

J1 connector 22pin-L

Phase failure protection detected
signal
Normal :5V(H)
Phase failure detection :about0.5V(L)

Direct-current voltage

IPL

J1 connector 11pin-L

The instantaneous power failure signal
of R0-T0 part
Power On : about0.5V(L)
Power Off : 5V(H)

Direct-current voltage

GS

J1 connector 20pin-L

Power-module protection
Under operation : about 5V(H)
Under a stop : about 0.5V(L)

Direct-current voltage

US
VS
WS

J1 connector 17pin-L
J1 connector 18pin-L
J1 connector 19pin-L

PWM signal
Upper arm ON : about 3.5V(L)
lower arm ON : about 5V(H)

GS

J1 connector 30pin-L

The trip distinguished by GA is canceled.
Normal : about 5V(H)
Under reset : about 0.5V(L)

0V

-3.3V

3.3V

3.5V

5V

0V

Upper arm ON Lower arm ON

Reset

Reset

5V

0.5V

0V