2 dayly and annual maintenance, 2 daily and annual maintenance – Hitachi SJ300 User Manual

Page 31

Advertising
background image

5- 2

5.2 Daily and annual maintenance

Interval

Item

Contents

D

A

Method

Criteria

Ambient

Environment

Check ambient temperature,

humidity, dust, corrosive gas, oil

mist, etc.

X

Refer to

2.1. Installation

Ambient temperature:

-10 ~ +50°C (no icing)

No condensation

Devices

overall

Check for abnormal vibrations

and noise.

X

Visual inspection

No abnormalities

Overall

Power supply

voltage

Check voltage between

input lines

X

Measure the voltage between

input terminals

No abnormalities and

within specifications

Overall

Megger check

(Power terminal - Earth)

X

Remove connector J61
Disconnect power line
Remove logic terminal
Make short circuit R, S, T, U,
V, W, P, PD ,N ,RB
Megger test between above
and earth

> 5Mohm

Check installation for looseness.

X

Tighten

No abnormalities

Check for evidence of over

heating in the various

components

X

Visual inspection

No abnormalities

Cleaning

X

Conductors /

cables

No change in shape?

X

Visual inspection

No abnormalities

No damage in coating?

X

Visual inspection

No abnormalities

Terminal block

No damage?

X

Visual inspection

No abnormalities

Mains

Inverter /

Converter

Tester check between each

terminal

X

Remove power cables
Measure resistance;

Each input

P, N

Each output

P, N

with 1ohm range

Refer to

“5.5 How to measure

inverter &

converter“ portion

DC bus capacitor

Check for leaking liquid

X

Visual inspection

No abnormalities

Check for swelling

X

Visual inspection

No abnormalities

Check for capacitance

X

With capacitance meter

85% or more of rated

capacitance

Relay, contactor

Check for stuttering noise during

operation

X

Aural inspection

No abnormalities

No damage of contact?

X

Visual inspection

No abnormalities

Resistors

Check for cracks or

changes in color

X

Visual inspection

No abnormalities

No open circuit?

X

Tester check

Tolerance of within

±

10% of rated value

Cooling fan

Check for abnormal

vibration and noise

X

Rotate manually

during power off

Smooth rotation and

no abnormalities

Cooling

Check for dust

X

Visual inspection

No abnormalities

Operation check

Check the balance of the output

voltage of each phase to phase

without motor.

X

Measure the output voltage

between U, V and W

Within 2% of voltage

difference between

each phases.

Control circuit

Perform a sequence protection

operation test and make sure
that there are no errors in the

protection and display circuits.

X

Simulate operation of the

protection circuit

Each protection should

be performed

Display

No illegible display;

No missing characters;

No segment failure of LEDs

X

Visual inspection

No abnormalities

Cleaning

X

LED

display

Meter

Working correct?

X

X

Visual inspection

Displays correct value

Overall

No abnormal vibration & noise?

X

Visual, aural inspection

No abnormalities

No abnormal smell?

X

Confirm the smell caused by

overheat, damage etc.

No abnormalities

Motor

Insulation

resistance

Megger check

All terminals together - Earth

X

Measure resistance;

Each input

Earth

With and without motor
cables

> 5Mohm