2 l300p – Hitachi SJ300 User Manual

Page 13

Advertising
background image

1 -10

1.2.2 L300P

Monitor code

Dis-
play

code

Function name

L300P monitor or data range

(digital operator)

Initial

data

Note

d001

Output frequency
monitor

0.00-99.99/100.0-400.0(Hz)

-

d002

Output current
monitor

0.0-999.9(A)

-

d003

Operation direction
monitor

F(forward)/o(stop)/r(reverse)

-

d004

PID feedback
monitor

0.00-99.99/100.0-999.9/1000. -9999 . /
1000-9999/ 100- 999 (10000-99900)

-

d005

Intelligent input
terminal monitor

-

d006

Intelligent output
terminal monitor

-

d007

Frequency
conversion monitor

0.00-99.99/100.0-999.9/1000. – 9999 . /
1000-3996

-

d013

Output voltage
monitor

0.0-600.0 V

-

d014

Electric power
monitor

0.0-999.9 kW

-

d016

Accumulated time
monitor during RUN

0.-9999./1000-9999/ 100- 999 h

-

d017

Power ON time
monitor

0.-9999./1000-9999/ 100- 999 h

-

d080

Number of trip time
monitor

0.-9999./1000-6553(10000-65530) (time)

-

d081

Trip monitor 1

Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)

-

d082

Trip monitor 2

Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)

-

d083

Trip monitor 3

Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)

-

d084

Trip monitor 4

Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)

-

d085

Trip monitor 5

Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)

-

d086

Trip monitor 6

Trip Code, frequency(Hz), current(A),
voltage(V),RUN time(h) power ON time(h)

-

d090

Warning monitor

Warning code

-

F001

Output frequency
setting

0.0, starting frequency-Max. frequency
(2

n d

max. frequency)(Hz)

0.00

F002

1

st

acceleration time

0.01-99.99/100.0-999.9/1000.-3600.(s)

30.00

F202

2

nd

acceleration time

0.01-99.99/100.0-999.9/1000. -3600. (s)

30.00

F003

1

st

deceleration time

0.01-99.99/100.0-999.9/1000. -3600. (s)

30.00

F203

2

nd

deceleration time

0.01-99.99/100.0-999.9/1000. -3600. (s)

30.00

F004

Operation direction
selection

00(forward)/01(reverse)

00

(Note1) Change mode during run by selection of b031 (software lock selection).

(Note2) Do not forget to press “STR” key when you change the display.

(Example) FW, terminal2, and 1: ON
Terminal 5, 4, 3 :OFF

ON

OFF

5 4

3 2

1

FW

(Example) Terminal2, 1:ON
AL :OFF

ON

OFF

12 11

AL

Advertising
This manual is related to the following products: