2.4 Check of the warning monitor contents

Warning message is come out when there is any contradiction.

Program lamp “PRG” is turned ON while warning (until the data are corrected).

Warning message and automatic rewriting

Warning

Related parameters

condit

ion

Base

001/ 201

Frequency upper limiter A061/A261

>

002/ 202

Frequency lower limiter A062/A262

>

004/ 204

Base frequency A003/A203

>

005/ 205

Output frequency F001, Multistage speed 0 A020/A220

>

006/ 206

Multistage speed 1-15 A021-A035

>

009

Orientation speed setting P015

>

Maximum
frequency A004/A204

012/ 212

Frequency lower limiter A062/A262

>

015/ 215

Output frequency F001, Multistage speed 0 A020/A220

>

016/ 216

Multistage speed 1-15 A021 - A035

>

Frequency upper limiter
A061/A261

021/ 221

Frequency upper limiter A061/A261

<

025/ 225

Output frequency F001 , Multi stage speed 0 A020/A220

<

Frequency lower limiter
A062/A262

031/ 231

Frequency upper limiter A061/A261

<

032/ 232

Frequency lower limiter A062/A262

<

035/ 235

Output frequency F001 , Multi stage speed 0 A020/A220

<

036

Multi stage speed 1-15 A021-A035

<

037

Jogging frequency A038

<

Start frequency b082

085/ 285

Output frequency F001 , Multi stage speed 0 A020/A220

<>

086

Multi stage speed 1-15 A021-A035

<>

Jump freq.
1/2/3 +/- Jump width
A063 +/ - A064
A065 +/- A066
A067 +/- A068 (note 1)

091/ 291

Frequency upper limiter A061/A261

>

092/ 292

Frequency lower limiter A062/A262

>

095/ 295

Output frequency F001 , Multi stage speed 0 A020/A220

>

096

Multi stage speed 1-15 A021-A035

>

Free v/f 7 b112

Free v/f frequency 1-6 b100,b102,b104,b106,b108,b110

>

Free v/f 1 b100

Free v/f frequency 2-6 b102,b104,b106,b108,b110

<

Free v/f frequency 1 b100

>

Free v/f 1 b100
Free v/f 2 b102

Free v/f frequency 3-6 b104,b106,b108,b110

<

Free v/f frequency 1,2 b100,b102

>

Free v/f 3 b104
Free v/f 3 b104

Free v/f frequency 4-6 b106,b108,b110

<

Free v/f frequency 1-3 b100,b102,b104

>

Free v/f 4 b106
Free v/f 4 b106

Free v/f frequency 5,6 b108,b110

<

Free v/f frequency 1-4 b100,b102,b104,b106

>

Free v/f 5 b108
Free v/f 5 b108

Free v/f frequency 6 b110

<

Free v/f 6 b110

110

Free v/f frequency 1-5 b100,b102,b104,b106,b108

>

Free v/f 6 b110

Free electronic thermal frequency 2,3 b017,b019

<

Free electronic thermal
frequency 1 b015

Free electronic thermal frequency 1 b015

>

Free electronic thermal frequency 3 b019

<

Free electronic thermal
frequency 2 b017

120

Free electronic thermal frequency 1,2 b015,b017

>

Free electronic thermal
frequency 3 b019

Warning is cleared when the setting fulfils the above condition.

Date will be changed automatically to the basic code.

(note 1)The jump frequency will be automaically re-written to the lowest jump frequency

(=jump frequency - jump width)