Function mode – Hitachi SJ300 User Manual

Page 17

Advertising
background image

1- 14

Function Mode

Code

Function name

L300P Setting range

Initial data

-FE/-FU/-FR

N o t e

C070

Data command

02(operator)/03(RS485)/04(option1)/05(option2)

02

C071

Communicating
transmission speed

02(loop-back test)/03(2400bps)/04(4800bps)/

05(9600bps)/06(19200bps)

04

C072

Communication code

1. - 32.

1.

C073

Communication bit

7(7bit)/8(8bit)

7

C074

Communication parity

00(no parity name)/01(even parity)/02(odd parity)

00

C075

Communication stop bit

1(bit)/2(bit)

1

C078

Communication waiting
time

0.-1000.(ms)

0.

C081

O adjustment

0.-9999./1000-6553(10000-65530)

Setting on
forwarding

C082

OI adjustment

0.-9999./1000-6553(10000-65530)

Setting on
forwarding

C083

O2 adjustment

0.-9999./1000-6553(10000-65530)

Setting on
forwarding

C085

Thermistor adjustment

0.0 - 1000.

105.0

C086

AM offset adjustment

0.0 - 10.0(V)

0.0

C087

AMI adjustment

0. - 2 5 5 .

80

C088

AMI offset adjustment

0. - 20.0( mA)

4.0

b034

RUN time/Power ON time
level

0.-9999./1000-6553(10000-65530)hr

0.

b035

Operation direction restrict

00(Reverse is valid)/01(Only forward)/02(Only reverse)

00

b036

Start reduced voltage

00(Start reduced voltage time small)

-06(Start reduced voltage time large)

06

b037

Display selection

00(all display)/01(each function display)/

02(User setting / main setting)

00

b080

AM adjustment

0. - 255.

180

b081

FM adjustment

0. - 255.

60

b082

Start frequency adjustment

0.10-9.99(Hz)

0.50

b083

Carrier frequency setting

0.5-12.0(kHz) Derating enable, <0.5-8.0kHz>

3.0

b084

Initialize mode

00(Trip history clear)/01(Data initialization)/

02(Trip history clear + data initialization)

00

b085

Country code for
initialization

00(Interior)/01(EC)/02(USA)

01/02/00

b086

Frequency scalar
conversion factor

0.1-99.9

1.0

b087

STOP key enable

00(valid)/01(invalid)

00

b088

Resume on FRS
cancellation mode

00(0Hz start)/01(Start f-equaling)

00

b090

BRD usage ratio

0.0-100.0(%)

0.0

b091

Stop mode selection

00(deceleration stop)/01(Free-run stop)

00

b092

Cooling fan control

00(Always ON)/01(ON during run, After power ON, then for 5 minutes

on stop is implied.)

00

b095

BRD selection

00(invalid)/01(valid<invalid during stop>)/

02(valid<valid during stop>)

00

b096

BRD ON level

330-380/660-760(V)

360/720

b098

Thermistor selection

00(invalid)/01(Positive temperature coefficient enable)/

02 (NTC enable)

00

b099

Thermistor error level

0. – 9999. ( ohm)

3000.

C061

Thermal warning level

0. – 100. ( %)

80

C091

Debug mode selection

00(No display)/01(Display)

00

C101

UP/DWN selection

00(No frequency data)/01(Keep frequency data)

00

C102

Reset selection

00(Trip cancel during ON)/01(Trip cancel during OFF)/

02(Valid only during trip<Cancel during ON>)

00

C103

Reset f frequency matching
selection

0 0 ( 0H z start)/01(Start f-equaling)

00

C121

O zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

C122

OI zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

C123

O2 zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

H003

1

s t

allowable motor

selection

0.20-90.0(kW) <0.20-160(kW)>

Set on

forwarding

H203

2

nd

allowable motor

selection

0.20-90.0(kW) <0.20-160(kW)>

Set on

forwarding

H004

1

s t

motor pole selection

2/4/6/8(pole)

4

H204

2

nd

motor pole selection

2/4/6/8(pole)

4

H006

1

s t

stabilized factor

0. - 255.

100.

H206

2

nd

stabilized factor

0. - 255.

100.

P001

Option1 operation selection
on error

00(TRP)/01(RUN)

00

P002

Option2 operation selection
on error

00(TRP)/01(RUN)

00

P031

Digital input option input
mode selection(Acc/Dec)

00(operation)/01(option1)/02(option2)

00

P044

DeviceNet running order of
monitoring timer setting

0.00-99.99s

1.00

P045

Setting in action of
abnormal communication

00(trip)/01(trip after deceleration stop)/02(invalid)/

03(free-run)04(deceleration stop)

0.

P046

Output assemble instance
Number setting

20,21,100

21

P047

Input assemble instance
Number setting

70,71,101

71

P048

Detect of idol mode for
motion setting

00(trip)/01(trip after deceleration stop)/02(invalid)/

03(free-run)04(deceleration stop)

01

P049

Pole setting of rotation
speed

0-38(even only)

0

(Note) < > indicate the setting range of 90 to 132kW
(Note1) P044-P049 are displayed o n a 0.4- 7 5kW model.

Analog meter setting

Communic

a

tion

function

The others

Advertising
This manual is related to the following products: