Debug mode, 1 monitor mode – Hitachi SJ300 User Manual

Page 25

Advertising
background image

3- 1

3.Debug Mode

Additional displays as follows can be seen by turning Debug mode ON (C091 ->1).

3.1 Monitor mode

No

Functional

Display code

SJ300/L300P A Monitor or data range

1

Control frequency monitor

d101

0.00-99.99/100.0-400.0Hz

2

Direct-current voltage monitor

d102

0.0-999.9V

3

BRD on-monitor

d103

0.00-99.99/100.0s

4

Electronic thermal monitor

d104

0.00-99.99/100.0%

5

Gate array trip factor monitor

d105

00-FF

6

MCU No. monitor

d106

0000-9999

d101 ( Output frequency monitor (Hz)): Monitor of the output frequency of the inverter.

d102 ( DC bus voltage monitor (V)): Monitor of the DC bus voltage (VPN) of the inverter.

d103 ( BRD ON monitor (s)): There is an integrated BRD circuit on 11kW and less for SJ300, and 15kW and less

for L300P series. You can find accumulated turning ON time for the integrated BRD

transistor.

d104 ( Electronic thermal monitor (%)):You can find the usage ratio of electronic thermal performance as %.

d105 (Trip cause monitor of gate array):There are 8 items of trips which are detected by the internal gate array

and these items are transmitted to MCU.

Bit7

bit6

Bit5

bit4

bit3

bit2

bit1

bit0

Contents of d105 are expressed in HEX.

(Example 1)

20

20 (HEX) = 00100000 (BIN)

bit5 = “1” -> IGBT error (V phase)

(Example 1)

62

62 (HEX) = 01100010 (BIN)

bit1, bit5, bit6 = “1 ” -> IGBT error (U, V, W phase)

d106(MCU No monitor): Display the software management number of MCU incorporated.

IGBT error
W phase
(E30)

IGBT error
V phase
(E30)

IGBT error
U phase
(E30)

Gate array
error
(E23)

Over
temperature
(E21)

Over voltage
(E07)

Under voltage
(E09)

Option
Ground fault
(E14)