1- 12

Function Mode

Code

Function name

L300P Setting range

Initial data

-FE/-FU/-FR

N o t e

A061

1

s t

frequency upper limiter

0.00, 1

s t

frequency lower limiter-maximum frequency(Hz)

0.00

A261

2

nd

frequency upper limiter

0.00, 2

nd

frequency lower limiter-2

nd

setting maximum

frequency(Hz)

0.00

A062

1

s t

frequency lower limiter

0.00, start frequency-maximum frequency(Hz)

0.00

A262

2

nd

frequency lower limiter

0.00, start frequency-2

nd

setting maximum frequency(Hz)

0.00

A063

Jump frequency1

0.00-99.99/100.0-400.0(Hz)

0.00

A064

Jump frequency Width 1

0.00-10.00(Hz)

0.50

A065

Jump frequency2

0.00-99.99/100.0-400.0(Hz)

0.00

A066

Jump frequency Width 2

0.00-10.00(Hz)

0.50

A067

Jump frequency3

0.00-99.99/100.0-400.0(Hz)

0.00

A068

Jump frequency Width 3

0.00-10.00(Hz)

0.50

A069

Acceleration stop frequency

0.00-99.99/100.0-400.0(Hz)

0.00

A070

Acceleration stop time

0.00-60.0(s)

0.0

A071

PID selection

00(invalid)/01(valid)

00

A072

PID-P gain

0.2-5.0

1.0

A073

PID-I gain

0.0-3600.(s)

1.0

A074

PID-D gain

0.00-100.0(s)

0.00

A075

PID scale

0.01-99.99

1.00

A076

PID feedback selection

00(feedback : OI)/01(feedback : O)

00

A081

AVR selection

00(ON always)/01(OFF always)/02(OFF on decelerating)

00/00/02

A082

Motor voltage selection

200/215/220/230/240, 380/400/415/440/460/480

(230/400)
(230/460)
(200/400)

A085

Operation mode selection

00(normal operation)/01(energy-saving operation)

00

A086

Energy-saving response-
accuracy adjustment

0.0-100.0

50.0

A092

Acceleration time2

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

A292

2

nd

acceleration time2

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

A093

Deceleration time2

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

A293

2

nd

deceleration time2

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

A094

2

nd

stage adjustable selection

00(change with 2CH terminal)/01(change with setting)

00

A294

2

nd

stage adjustable

selection(2

nd

motor)

00(change with 2CH terminal)/01(change with setting)

00

A095

2

nd

acceleration frequency

0.00-99.99/100.0-400.0(Hz)

0.00

A295

2

nd

acceleration

frequency(2

nd

motor)

0.00-99.99/100.0-400.0(Hz)

0.00

A096

2

nd

deceleration frequency

0.00-99.99/100.0-400.0(Hz)

0.00

A296

2

nd

deceleration frequency

(2

nd

motor)

0.00-99.99/100.0-400.0(Hz)

0.00

A097

Acceleration pattern selection

00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)

00

A098

Deceleration pattern selection

00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)

00

A101

OI start

0.00-99.99/100.0-400.0(Hz)

0.00

A102

OI end

0.00-99.99/100.0-400.0(Hz)

0.00

A103

OI start rate

0.-100. ( %)

20.

A104

OI end rate

0.-100. ( %)

100.

A105

OI start selection

00(external start frequency)/01(0Hz)

01

A111

O2 start

-400.--100./-99.9-0.00-99.9/100.-400.(Hz)

0.00

A112

O2 end

-400.--100./-99.9-0.00-99.9/100.-400.(Hz)

0.00

A113

O2 start rate

-100. - 100. (%)

-100.

A114

O2 end rate

-100. - 100. (%)

100.

A131

Acceleration curve constant

01(small swelling)-10(large swelling)

02

A132

Deceleration curve constant

01(small swelling-10(large swelling)

02

b001

Retry selection

00(trip)/01(0Hz start)/02(start after equal frequency)/

03(trip after equaling frequency and deceleration stop)

00

b002

Allowable under-voltage
power failure time

0.3-1.0(s)

1.0

b003

Retry wait time

0.3-100.(s)

1.0

b004

Instantaneous power-
failure/under-voltage trip
during stop

00(invalid/01(valid)/

02(invalid during stop and deceleration by stop command)

00

b005

Instantaneous power-
failure/under-voltage
retry time selection

00(16 times)/01(free)

00

b006

Open-phase selection

00(invalid)/01(valid)

00

b007

Frequency setting to match

0.00-99.99/100.0-400.0(Hz)

0.00

b012

Electronic thermal level

0.2*constant current-1.20*constant current(A)

Rated
Current of
inverter

b212

Electronic thermal level
(2

nd

motor)

0.2*constant current-1.20*constant current(A)

Rated
Current of
inverter

b013

Electronic thermal
characteristic selection

00/(reduced characteristic)01(constant torque characteristic)/

02(free setting)

01/01/00

b213

Electronic thermal
characteristic selection
(2

nd

motor)

00/(reduced characteristic)01(constant torque characteristic)/

02(free setting)

01/01/00

b015

Free electronic thermal
frequency 1

0.-400.(Hz)

0.

b016

Free electronic thermal
current 1

0.0-1000.(A)

0.0

b017

Free electronic thermal
frequency 2

0.-400.(Hz)

0.

b018

Free electronic thermal
current 2

0.0-1000. (A)

0.0

b019

Free electronic thermal
frequency 3

0.-400.(Hz)

0.

b020

Free electronic thermal
current 3

0.0-1000.(A)

0.0

Upper and lower

limiter

/

jump

frequency

PID control

External frequency

adjustment

AVR

Operation mode/ adjustable function

Accel

Decel

Instantaneous power failure

restart

Electronic thermal

Advertising