1- 13

Function Mode

Code

Function name

L300P Setting range

Initial data

-FE/-FU/-FR

N o t e

b021

Overload restriction
selection

00(invalid)/01(enabled on acceleration / constant speed)/02(enabled

on constant speed)

01

b022

Overload restriction level

0.50* rated current-1.50* rated current(A)

Rated

current of

inverter

x 1.20

b023

Overload restriction limit
constant

0.10-30.00(s)

1.00

b024

Overload restriction 2
selection

00(invalid)/01(valid on acceleration / constant speed)/02(valid on

constant speed)

01

b025

Overload restriction level 2

0.50*rated current-1.50*rated current(A)

Rated

current of

inverter

x1.20

b026

Overload restriction
constant 2

0.10-30.00(s)

1.00

b031

Software lock mode
selection

00(impossible to change the data except this item when SFT terminal
is ON)/01(impossible to change the data except setting frequency
item when SFT terminal is ON)/02(impossible to change the data
except this item)/03(impossible to change the data except setting
frequency item)/10(possible to change data on operating)

01

b100

Free V/f frequency 1

0.- Free V/f frequency2(Hz)

0.

b101

Free V/f voltage 1

0.-800.0(V)

0.0

b102

Free V/f frequency 2

0.- Free V/f frequency3(Hz)

0.

b103

Free V/f voltage 2

0.-800.0(V)

0.0

b104

Free V/f frequency 3

0.- Free V/f frequency4(Hz)

0.

b105

Free V/f voltage 3

0.-800.0(V)

0.0

b106

Free V/f frequency 4

0.- Free V/f frequency5(Hz)

0.

b107

Free V/f voltage 4

0.-800.0(V)

0.0

b108

Free V/f frequency 5

0.- Free V/f frequency6(Hz)

0.

b109

Free V/f voltage 5

0.-800.0(V)

0.0

b110

Free V/f frequency 6

0.- Free V/f frequency7(Hz)

0.

b111

Free V/f voltage 6

0.-800.0(V)

0.0

b112

Free V/f frequency 7

0.-400.(Hz)

0.

b113

Free V/f voltage 7

0.-800.0(V)

0.0

C001

Intelligent input 1 setting

18

C002

Intelligent input 2 setting

16

C003

Intelligent input 3 setting

03/13/03

C004

Intelligent input 4 setting

02

C005

Intelligent input 5 setting

0 1 / (RV:Reverse is valid)/02(CF1:Multi-speed1)/ 0 3 ( C F 2 : M u l t i - s p e e d 2 ) /
04(CF3:Multi-speed3)/ 05(CF4:Multi-speed4)/ 0 6 (JG:Jogging)/
07(DB:External DC braking)/08(SET:2

nd

control)/

09(2CH:two-stage adjustable speed)/11(FRS:Free-run)/
12(E X T : E x t e r n a l t r i p ) / 1 3 ( USP:Unattended start protection)/
14(CS:commercial change)/15(SFT:software lock)/
16(AT:Analog input voltage/current select)/18(RS:Reset inverter)/
20(STA:3wire run)/ 21(STP:3wire keep)/22(F/R:3wire forward/reverse)/
23(PID:PID selection valid/invalid)/24(PIDC:PID integrating reset)/
2 7 ( U P : R e m o t e c o n t r o l U P f u n c t i o n ) /
28(DWN:Remote control DOWN function)/
29(U D C : R e m o t e c o n t r o l d a t a c l e a r ) / 3 1 ( OPE:Force operate o p e ) /
32(SF1:Multi-speed bit1)/
33(SF2:Multi-speed bit2)/34(SF3:Multi-speed bit3)/
35(SF4:Multi-speed bit4)/36(SF5:Multi speed bit5)/
37(SF6:Multi-speed bit6)/38(SF7:Multi-speed bit7)/
39(OLR:Overload restriction change)/no(NO:No assign)

01

C011

Intelligent input1 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C012

Intelligent input2 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C013

Intelligent input3 a/b
(NO/NC) selection

00(NO)/01(NC)

00/01/00

C014

Intelligent input4 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C015

Intelligent input5 a/b
(NO/NC) selection

00(NO)/01(NC)

00

C019

Input FW a/b (NO/NC)
Selection

00(NO)/01(NC)

00

C021

Intelligent output 11 setting

01

C022

Intelligent output 12 setting

00

C026

Alarm relay output

00( RUN:running)/01(FA1:Frequency arrivaltype1 signal)/
02(FA2:frequency arrival type2 signal)/03(OL:Overload advance
notice signal)/04(OD:Output deviation for PID control)/05(AL:Alarm
signal)/06(FA3:Only setting frequency)/08( IP:On instantaneous stop/
09( UV:Under voltage)/11(RNT:RUN time over)/12(ONT:ON time
over)/
13( THM:thermal caution)

05

C027

FM selection

00(Output frequency)/01(Output current) /
03(Digital output frequency)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)

00

C028

AM selection

00(Output frequency)/01(Output current)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)

00

C029

AMI selection

00(Output frequency)/01(Output current)/04(Output voltage)/
05(Input electric power)/06(Thermal load rate)/07(LAD frequency)

00

C031

Intelligent output 11 a/b

00(NO)/01(NC)

00

C032

Intelligent output 12 a/b

00(NO)/01(NC)

00

C036

Alarm relay output a/b

00(NO)/01(NC)

01

C040

Overload advance notice
signal output mode

00(On accel. And decel, constant speed)/01(Only constant speed)

01

C041

Overload advance notice
level

0.0-2.0*rated current(A)

Inverter

rated current

C042

Frequency arrival setting
for acceleration.

0.00-99.99/100.0-400.0(Hz)

0.00

C043

Arrival frequency setting for
deceleration.

0.00-99.99/100.0-400.0(Hz)

0.00

C044

PID deviation setting level

0.0-100.0(%)

3.0

Overload limit

Lock

Free V/f setting

Intelligent input terminal setting

Intelligent output terminal setting

Output terminal state setting,

Output level setting

Input terminal setting

intelligent