Power source, System power connections, Figure 14. power supply front panel – Fusion F300S User Manual

Page 50

Advertising
background image

50

F300S/F300SQ Ultraviolet Lamp System

Power Source

NOTE: If a line voltage greater than 230V and a frequency of 50 Hz is used, see
the

“F300S Relay Coil Resistor Assembly Installation” on page 53

at the end of

this chapter.

System Power Connections

Figure 14. Power Supply Front Panel

Listed current ratings indicate current demands during normal full-power operation.
Your customer-supplied wiring and circuit breaker or fuses should be sized to allow
for heavier current draw at startup. Current ratings are the same for 50 Hz or 60 Hz
systems. The recommended power cord to wire to P101 is:

CAUTION: Measure the main single-phase voltage
of your plant facilities to ensure that it conforms to
the factory-wired operating voltage specified on the
equipment label (rear panel of power supply).
Available line voltage should be within 10% of the
nominal operating voltage.

Fusion UV equipment must be connected in
accordance with local wiring codes. Use applicable
standards for wire sizes, fuse sizes, and disconnect
box locations. Each power supply requires a
separate, fused single-phase circuit with a line
disconnect.

F3q0004